4-14
4.3.2 Function mode
Setting of the output frequency
Setting the output frequency of the motor.
The output frequency is set by F001, when the frequency command
select (A001) is set to 02.
Please refer to the frequency command select (A001) about other
methods of frequency setting.
When a frequency is set in F001, the same value is automatically set in both Multispeed 0 (A020) and the
second set of motor data multispeed 0 (A220) when the SET terminal is ON.
In the case of using SET, you will need to assign 08(SET) to an intelligent input terminal.
Set item
Function code
Data
Contents
Output frequency
setting
F001
Multistage speed
zero
A020/A220
0.0, start frequency-First/Second
maximum frequency
Unit : Hz
“F001” = “A020”
Second control setting of “F001” =
“A220”
Operation direction
This is effective when the operating command is set by the digital operator.
Function code
Data
Contents
00
Forward
F004
01
Reverse
Selection with limits of operation direction
The direction of the motor can be restricted.
Function code
Data
Contents
00
Forward/reverse is effective.
01
Only forward
b035
02
Only reverse
Frequency command selection
Select the method of frequency command.
When 0-10Vdc is inputted to the frequency command by 02-L terminal,
operation direction of motor reverses.
On output frequency monitor d001, you can’t get information about forward/reverse. So be sure with operation
direction monitor d002.
Function code
Data
Contents
00
Setting frequency with the potentiometer the digital operator has.
01
Setting frequency with control terminals (Terminals: O-L, OI-L, O2-L)
02
Setting frequency with digital operator(F001), remote operator.
03
Setting frequency with RS485 terminals for communication.
04
Setting frequency with option board 1.
A001
05
Setting frequency with option board 2.
Chapter4 Explanation of function
F004: Operation direction select
Relation code
F001 :Output frequency setting
A001 :Frequency command select
A020/A220: 1
st
/2
nd
multistage speed
zero
C001-C005: Intelligent input terminal
Relation code
b035: Selection with limits
of operation direction
Relation code
A001:Frequency command
selection
Relation code