—————— TPD32-EV ——————
124
After the completion of the Speed self tune
by the Drive, the new identified parameter values (“Nw” suffix) can
be compared with values prior to the procedure, by browsing the subsequent menu entries. Parameters in this
menu are read only. Editing of individual parameters must be done in their specific menus.
New parameters can be accepted all togetheter by entering “
Take val
” after disabling the Drive. In this case,
prior values are overwritten. “
Self tuning
” can be repeated, whether values from the previous trial have been
accepted or not.
n
ote
!
“
Take val
” does not store values in non-volatile memory, so values are lost if Drive power
is cycled off and on. You need to enter
Save parameters
in the START UP or SPEC FUNC
-
TIONS menu to permanently store values in non-volatile memory.
In case of extreme parameter ranges, error messages can occurr. Repeat execution in this case. If the error mes
-
sage is persistent, keep default values and use manual tuning of speed regulator (section 5.3.6 Manual tuning
of the regulators).
List of self tune error messages
Generic messages
Description
Note
“Drive disabled”:
Provide enable input by setting terminal 12 high.
“Not ready”:
“
Take val
” can not be executed because the measurement has not been completed cor
-
rectly. Repeat self tune command.
“Time out”:
Measurement has not been completed in the proper time
“Start ?”:
Press E to confirm start of measurement.
“Tuning aborted”:
Measurement aborted by user (CANC button has been pressed).
“Set Main cmd=Dig”:
Go to CONFIGURATION menu and set
Main commands
= digital.
“Set Ctrl=Local”:
Go to CONFIGURATION menu and set
Control mode
= Local.
Measurement error messages
These messages may occour when extreme parameter values have to be identified. It can be useful to retry the
self tune command when any of the following messages occours. If messages persist, alternative manual tuning
procedures should be used.
Description
Note
“Over speed”
“Drive stalled”:
Increase value of parameter
Test T curr lim
and repeat
Self tuning
“Load applied”:
Nominal zero load torque at standstill was detected.
Self tuning
is impossible for this
type of load.
“T curr too high”:
Reduce value of
Test T curr lim
parameter for
Self tuning
“Friction null”:
Value of friction is zero or lower than the accuracy limit of the control system
Summary of Contents for TPD32-EV-...-2B
Page 1: ... Instruction manual Industrial Application DC drives TPD32 EV ...
Page 372: ... TPD32 EV 372 9 BLOCK DIAGRAM 9 1 CONTROL BLOCK DIAGRAMS ...
Page 373: ... Instruction manual 373 ...
Page 374: ... TPD32 EV 374 ...
Page 375: ... Instruction manual 375 ...
Page 376: ... TPD32 EV 376 ...
Page 377: ... Instruction manual 377 ...
Page 378: ... TPD32 EV 378 ...
Page 379: ... Instruction manual 379 ...
Page 380: ... TPD32 EV 380 ...
Page 381: ... Instruction manual 381 ...
Page 382: ... TPD32 EV 382 ...
Page 383: ... Instruction manual 383 ...
Page 384: ... TPD32 EV 384 ...
Page 385: ... Instruction manual 385 ...
Page 386: ... TPD32 EV 386 ...
Page 387: ... Instruction manual 387 ...
Page 388: ... TPD32 EV 388 ...
Page 389: ... Instruction manual 389 ...
Page 390: ... TPD32 EV 390 ...
Page 391: ... Instruction manual 391 ...
Page 392: ... TPD32 EV 392 ...
Page 393: ... Instruction manual 393 ...
Page 394: ... TPD32 EV 394 ...
Page 395: ... Instruction manual 395 ...
Page 396: ... TPD32 EV 396 ...
Page 397: ... Instruction manual 397 ...
Page 398: ... TPD32 EV 398 ...
Page 399: ... Instruction manual 399 ...
Page 400: ... TPD32 EV 400 ...
Page 401: ... Instruction manual 401 ...
Page 402: ... TPD32 EV 402 ...
Page 501: ... Instruction manual 501 APPENDIX 3 ACCESSORIES A3 1 EAM Adapter Kit EAM1579 EAM1580 ...
Page 503: ......