—————— TPD32-EV ——————
270
zero speed, the converter is blocked after a timespan set by
Spd
0 trip delay
. The relay contact between the terminals 75/76
opens after a timespan set by
Trip cont delay
.
Fast stp & spd 0
The Fast Stop command determines the behavior. If the Fast
Stop command is present (digital or via terminal strip; f.e. with
0 V on the terminal 14) and the drive is stopped, the converter is
blocked and the contact is open.When the Fast Stop command
is disabled (i.e. with 24 V on the terminal 14), The converter is
enabled and the contact is closed. Entering the Fast Stop com
-
mand, when the zero speed has been reached, the converter is
blocked after a timespan set with
Spd 0 trip delay.
Fst / stp & spd 0
The Fast Stop and Start commands determine the behavior. When
the Stop or Fast Stop commands are present and the drive is stopped,
the converter is blocked and the contact is open. When the Start
command is given or when the Fast Stop command is disabled, the
converter is blocked and the contact is closed. When the Start com
-
mand is disabled or when a Fast Stop command is entered and after
reaching zero speed, the converter is stopped after a timespan set
by
Spd 0 trip delay
. The relay contact between the terminals
75/76 opens after a timespan set by
Trip cont delay
.
Spd 0 trip delay
Delay time in ms between reaching zero speed and disenabling of the converter.
Trip cont delay
Delay time in ms between disenabling and opening of the contact between the terminals
75 and 76.
Jog stop control
OFF
The behavior selected by
Stop mode
has no influence on the
Jog function.
ON
The behavior selected by
Stop mode
is active also on the Jog
function.
The mentioned “contact” can be either the one between the terminals 75/76 or a digital output (option TBO).
In both cases during the display of the message the “
Stop control
” parameter must be selected. The function
is factory set on the relay contact. The open contact, mentioned in the description, corresponds to 0 V on the
digital output, while the closed contact corresponds to +24 V on the digital output.
n
ote
!
At all the described possiblilities for
Stop mode
, the stop signal on the terminal 13 must be
present. With
Main commands
= Digital, it is necessary to select
Enable drive
parameter
= Enabled via keypad or Bus.
Summary of Contents for TPD32-EV-...-2B
Page 1: ... Instruction manual Industrial Application DC drives TPD32 EV ...
Page 372: ... TPD32 EV 372 9 BLOCK DIAGRAM 9 1 CONTROL BLOCK DIAGRAMS ...
Page 373: ... Instruction manual 373 ...
Page 374: ... TPD32 EV 374 ...
Page 375: ... Instruction manual 375 ...
Page 376: ... TPD32 EV 376 ...
Page 377: ... Instruction manual 377 ...
Page 378: ... TPD32 EV 378 ...
Page 379: ... Instruction manual 379 ...
Page 380: ... TPD32 EV 380 ...
Page 381: ... Instruction manual 381 ...
Page 382: ... TPD32 EV 382 ...
Page 383: ... Instruction manual 383 ...
Page 384: ... TPD32 EV 384 ...
Page 385: ... Instruction manual 385 ...
Page 386: ... TPD32 EV 386 ...
Page 387: ... Instruction manual 387 ...
Page 388: ... TPD32 EV 388 ...
Page 389: ... Instruction manual 389 ...
Page 390: ... TPD32 EV 390 ...
Page 391: ... Instruction manual 391 ...
Page 392: ... TPD32 EV 392 ...
Page 393: ... Instruction manual 393 ...
Page 394: ... TPD32 EV 394 ...
Page 395: ... Instruction manual 395 ...
Page 396: ... TPD32 EV 396 ...
Page 397: ... Instruction manual 397 ...
Page 398: ... TPD32 EV 398 ...
Page 399: ... Instruction manual 399 ...
Page 400: ... TPD32 EV 400 ...
Page 401: ... Instruction manual 401 ...
Page 402: ... TPD32 EV 402 ...
Page 501: ... Instruction manual 501 APPENDIX 3 ACCESSORIES A3 1 EAM Adapter Kit EAM1579 EAM1580 ...
Page 503: ......