—————— Instruction manual ——————
133
+
S
+
T
Field current Limits
Flux current max
Flux current min
Spd=0 Thr
Voltage reg P / I Base
Field reg P / I Base
Field controller
Field reg P / I
I field curve
Voltage regulator
T
M
C1
D1
Output Voltage
Flux
current
min
Flux
current
max
Energy saving
Field economy
Fld reg P gain
2 %
Fld reg I gain
1 %
Flux current %
Nom flux curr
10 A
Motor field curr
10 A
Ifield cnst40
40 %
Ifield cnst90
90 %
Ifield cnst70
70 %
Voltage P
30 %
Voltage I
40 %
Output voltage
Max. out voltage
500 V
Out vlt level
100 %
Flux current max
100 %
Flux current min
70 %
Enable flux weak
Disabled
Speed-0 f weak
Enabled
Motor field curr
10 A
Flux reg mode
Speed zero level
10 rpm
Set flux/if
0
Reset flux / if
0
Flux P base
3277
Flux I Base
3277
Voltage P base
1.8 A/V
Voltage I base
13.0909 A/V*ms
Enable flux reg
Flux reference
S
-
-
Figure 5.3.7.2: Blocks diagrams of field current regulator
Tuning procedure:
- Reset the curve flux/current via the
Reset flux
/
if
command (FLUX REGULATION \ Flux / if curve menu )
- Set the Motor nom flux
:
Motor nom flux
parameter (FLUX REGULATION menu)
- Set the output voltage via the
Max out voltage
parameter (CONFIGURATION menu) and the correspondent
percentage (100%) in the
Out vlt level
parameter (FLUX REGULATION menu)
- Set the Flux regulator
Flux reg mode
= Constant current (FLUX REGULATION menu)
- Set the flux percentage at 100% via the
Flux current max
parameter (FLUX REGULATION menu)
- Operate the Drive speed, so that the
Armature voltage
(MONITOR\Measurements menu) corresponds to
the value previously set in
Max out voltage
(CONFIGURATION menu).
- Via the
Flux current max
parameter decrease the voltage displayed in
Armature voltage
, up to obtain an
output voltage equal to the 90% of
Max out voltage
.
Carry out the reading of the current in the
Flux current
parameter (FLUX REGULATION menu) and insert
it in the
I field cnst 90
parameter (FLUX REGULATION\Flux if curve menu).
- Via the
Flux current max
parameters decrease the voltage displayed in
Armature voltage
, to obtain an
output voltage equal to the 70% of
Max out voltage
.
Carry out the reading of the current circulating in the
Flux current
parameter (FLUX REGULATION menu)
and insert it in the
I field cnst 70
parameter (FLUX REGULATION\Flux if curve menu).
- Via the
Flux current max
parameters decrease the voltage displayed in
Armature voltage
, to obtain an
output voltage equal to the 40% of
Max out voltage
.
Carry out the reading of the current circulating in the
Flux current
parameter (FLUX REGULATION menu)
and insert it in the
I field cnst 40
parameter (FLUX REGULATION\Flux if curve menu).
- Disable the converter
Summary of Contents for TPD32-EV-...-2B
Page 1: ... Instruction manual Industrial Application DC drives TPD32 EV ...
Page 372: ... TPD32 EV 372 9 BLOCK DIAGRAM 9 1 CONTROL BLOCK DIAGRAMS ...
Page 373: ... Instruction manual 373 ...
Page 374: ... TPD32 EV 374 ...
Page 375: ... Instruction manual 375 ...
Page 376: ... TPD32 EV 376 ...
Page 377: ... Instruction manual 377 ...
Page 378: ... TPD32 EV 378 ...
Page 379: ... Instruction manual 379 ...
Page 380: ... TPD32 EV 380 ...
Page 381: ... Instruction manual 381 ...
Page 382: ... TPD32 EV 382 ...
Page 383: ... Instruction manual 383 ...
Page 384: ... TPD32 EV 384 ...
Page 385: ... Instruction manual 385 ...
Page 386: ... TPD32 EV 386 ...
Page 387: ... Instruction manual 387 ...
Page 388: ... TPD32 EV 388 ...
Page 389: ... Instruction manual 389 ...
Page 390: ... TPD32 EV 390 ...
Page 391: ... Instruction manual 391 ...
Page 392: ... TPD32 EV 392 ...
Page 393: ... Instruction manual 393 ...
Page 394: ... TPD32 EV 394 ...
Page 395: ... Instruction manual 395 ...
Page 396: ... TPD32 EV 396 ...
Page 397: ... Instruction manual 397 ...
Page 398: ... TPD32 EV 398 ...
Page 399: ... Instruction manual 399 ...
Page 400: ... TPD32 EV 400 ...
Page 401: ... Instruction manual 401 ...
Page 402: ... TPD32 EV 402 ...
Page 501: ... Instruction manual 501 APPENDIX 3 ACCESSORIES A3 1 EAM Adapter Kit EAM1579 EAM1580 ...
Page 503: ......