How to calculate Input 1 compare and Input 1 cp error parameters:
Input 1 compare = (Compare value ) * 10000 / (Full range value)
Input 1 error = (Tolerance half window) 10000 / (Full range value)
Example 1:
Select analog input 1 to
Ramp ref 1
Speed base value
equal to 1500 [RPM]
10Volt or 20 mA on analog input 1 (Ramp ref 1=Speed base value).
The application requires a signaling at 700 [RPM] via a digital output, with a tolerance window equal to 100 [RPM]
Input 1 cp match
assigned to a programmable digital output.
Input 1 compare
= 700 * 10000 / 1500 = 4667
Input 1 cp error
= 100 * 10000 / 1500 = 666
Example 2:
Select analog input 1 to
Ramp ref 1
Speed base value
equal to 1500 [RPM]
10Volt or 20 mA on
Analog input 1
(
Ramp ref 1
=
Speed base value
).
The application requires a signaling at –700 [RPM] via LAN, with a tolerance window equal to ±100 [RPM]
Input 1 compare
= -700 * 10000 / 1500 = -4667
Input 1 cp error
= 100 * 10000 / 1500 = 666
Example 3:
Select analog input 1 to
Pad 0
10Volt or 20 mA on
Analog input 1
corresponds to Pad 0=2047.
The application requires a signaling at 700 [count] via a digital output, with a tolerance window equal to ±50 [count]
Input 1 cp match
assigned to a programmable digital output
Input 1 compare
= 700 * 10000 / 2047 = 3420
Input 1 cp error
= 50 * 10000 / 2047 = 244
Example 4:
Select analog input 1 to
PID feedback
10Volt or 20 mA on
Analog input 1
corresponds to
PID feedback
=10000.
The application requires a signaling at 4000 [count] via a digital output, with a tolerance band equal to ±1000 [count]
Input 1 cp match
assigned to a programmable digital output
Input 1 compare
= 4000 * 10000 / 10000 = 4000
Input 1 cp error
= 1000 * 10000 / 10000 = 1000
Example 5:
Select input 1 to
T current lim
10Volt or 20 mA on
Analog input 1
corresponds to
T current lim
= 100 [%]
The application requires a signaling at 50 [%] via a digital output, with a tolerance band equal to ±2 [%]
Input 1 cp match
assigned to a programmable digital output
Input 1 compare
= 50 * 10000 / 100 = 5000
Input 1 cp error
= 2 * 10000 / 100 = 200
Summary of Contents for TPD32-EV-...-2B
Page 1: ... Instruction manual Industrial Application DC drives TPD32 EV ...
Page 372: ... TPD32 EV 372 9 BLOCK DIAGRAM 9 1 CONTROL BLOCK DIAGRAMS ...
Page 373: ... Instruction manual 373 ...
Page 374: ... TPD32 EV 374 ...
Page 375: ... Instruction manual 375 ...
Page 376: ... TPD32 EV 376 ...
Page 377: ... Instruction manual 377 ...
Page 378: ... TPD32 EV 378 ...
Page 379: ... Instruction manual 379 ...
Page 380: ... TPD32 EV 380 ...
Page 381: ... Instruction manual 381 ...
Page 382: ... TPD32 EV 382 ...
Page 383: ... Instruction manual 383 ...
Page 384: ... TPD32 EV 384 ...
Page 385: ... Instruction manual 385 ...
Page 386: ... TPD32 EV 386 ...
Page 387: ... Instruction manual 387 ...
Page 388: ... TPD32 EV 388 ...
Page 389: ... Instruction manual 389 ...
Page 390: ... TPD32 EV 390 ...
Page 391: ... Instruction manual 391 ...
Page 392: ... TPD32 EV 392 ...
Page 393: ... Instruction manual 393 ...
Page 394: ... TPD32 EV 394 ...
Page 395: ... Instruction manual 395 ...
Page 396: ... TPD32 EV 396 ...
Page 397: ... Instruction manual 397 ...
Page 398: ... TPD32 EV 398 ...
Page 399: ... Instruction manual 399 ...
Page 400: ... TPD32 EV 400 ...
Page 401: ... Instruction manual 401 ...
Page 402: ... TPD32 EV 402 ...
Page 501: ... Instruction manual 501 APPENDIX 3 ACCESSORIES A3 1 EAM Adapter Kit EAM1579 EAM1580 ...
Page 503: ......