Feeding
125
5. In
feed. speed
enter the desired value.
6. Enter the desired value in
break
.
<group A>
after: 03 h 00 min
yesterday: 80 %
feed. speed: [70]%
break w.o. add.: 3
break w. add.: 1
Default value:
70 %
Range:
0 % to 99 %
Note:
The average, animal-specific feeding speed of the
current feeding day is daily compared in the evening
with the average of the previous three days.
Example:
Animal’s average feeding speed of the previ-
ous three days is 1 (one) liter per minute. The alarm lev-
el is set to 70 %. If the average, animal-specific feeding
speed of the current feeding day drops to 0.6 liters per
minute, the alarm level (70 % of 1 liter = 0.7 liters) is not
achieved. An alarm is given.
<group A>
after: 03 h 00 min
yesterday: 80 %
feed. speed: 70 %
break w.o. add.: [3]
break w. add.: 1
Note:
If the automatic feeder is equipped with an
ad-
ditive dispenser, in
break w.o. add.
(= break without ad-
ditive) and
break w. add.
(= break with additive) you
must enter how often feeding with or without additive
may be broken off before an alarm is given.
Default value:
Break without additive: 3
Break with additive: 1
Range:
0 to 99
Summary of Contents for TAK5-CH1-25
Page 38: ...38 Operation ...
Page 54: ...54 Start up ...
Page 70: ...70 Setup ...
Page 84: ...84 Device data ...
Page 90: ...90 Calibration ...
Page 150: ...150 Cleaning ...
Page 170: ...170 Animal control ...
Page 192: ...192 Failures and warnings ...
Page 196: ...196 Care and maintenance plan Routine tasks ...
Page 215: ......
Page 218: ...218 Annex 16 3 5 Template for individual feeding plan ...
Page 219: ...Annex 219 16 4 Basic principle of interval feeding ...
Page 222: ...222 Annex ...