Meeting Site Requirements
Extreme Networks Consolidated XOS Hardware Installation Guide
23
WARNING!
The chassis does not have a switch for turning the unit on and off. Power to the chassis is disconnected by
removing the wall plug from the electrical outlet. Ensure that all plugs and electrical outlets are easily accessible.
Securing the Rack
The rack should be attached to the wiring closet floor with 3/8-inch (9.5 mm) lag screws or equivalent
hardware. The floor under the rack should be level within 3/16-inch (5 mm). Use a floor-leveling
cement compound if necessary or bolt the racks to the floor as shown in
Figure 4
.
Figure 4: Properly secured rack
Brace open distribution racks if the channel thickness is less than 1/4 inch (6.4 mm).
SPG_007
Secure to floor
with 3/8-inch lag screws or bolts