23
23
EN
ESIM384 Installation and Configuration Manual v1.1
Parallel Wiring Method
ESIM384
Max. cable length:
up to 100m (328.08ft)
EPGM1
EPGM1
EKB2/EKB3
EKB2/EKB3
EKB2/EKB3
Elan3-alarM
EKB2/EKB3
attEntIon:
the cable between eSIM384 and each RS485 device must be of the same length and can NOt exceed 100m (328.08ft).
attEntIon:
When wiring more than 1 keypad and/or ePGM1 module, please ensure that the set address of each keypad and/or ePGM1
module is different.
notE:
If necessary, the RS485 devices can be powered from an external 12-14V DC power supply instead of AUX+ and AUX- terminals
notE:
You may connect only 1 eKB2/eKB3 keypad or a mixed combination of eKB2 and eKB3 keypads. the combination can consist of
up to 4 keypads in total.
For more details on RS485 interface, please refer to
32.1. rS485 Interface
2.3.8. rInG/tIP
RING
TIP
ESIM384
to PSTN
(landline)
16
attEntIon:
the
tIP/rInG
connectors and PStN module
are NOt included in a standard eSIM384 alarm system unit.
these components are op tional and can be implemented on
request in advance.