ESIM384 Installation and Configuration Manual v1.1
2.3. Wiring Diagrams
2.3.1. General Wiring
BELL- BELL+
G
Y
C2
AU
X-
AU
X+
AC
/D
C
AC
/D
C
Z1 CO
M
Z2 Z3 CO
M
Z4
+5
V
BU
Z-
C1
BU
Z+
CO
M
CO
M
DA
TA
CO
M
Z6 Z7
Z8
Z5
BUZ
SIREN/BELL
iButton®
key reader
Temperature sensor
EKB2
EKB3
EPGM1
Z1 Z2
Backup Battery
12V 1.3-7Ah
Metal cabinet
PE terminal
Relay
module
1A max.
Z4
Z3
Z5 Z6
Fuse 500 mA
~230V 50/60Hz
~16-24V
AKU+
AKU-
5,6 kΩ
5,6 kΩ
Z7 Z8
5,6 kΩ
5,6 kΩ
5,6 kΩ
5,6 kΩ
5,6 kΩ
5,6 kΩ
1
2
3
4
5
6
7
8
9
*
0
#
2
2.3.2. Zone Connection types
type 1
example of 4-wire smoke detector wiring
Z1
CO
M
AUX+
+Vin
GND
C1
COM
NO
5,6 kΩ
3
8-Zone mode: Nor-
mally open contact
with 5,6KΩ end-of-
line resistor.
Z
COM
NO
EOL 5.6K
Z
COM
NC
EOL 5.6K
Z
COM
NC
NC
5.6K
3.3K
Z
COM
NC
3.3K
EOL 5.6K
TAMPER
Z
COM
NC
3.3K
NC
5.6K
EOL 5.6K
TAMPER
type 2
example of magnetic door contact wiring
COM
NC
Magnet
CO
M
Z1
5,6 kΩ
Z
COM
NO
EOL 5.6K
Z
COM
NC
EOL 5.6K
Z
COM
NC
NC
5.6K
3.3K
Z
COM
NC
3.3K
EOL 5.6K
TAMPER
Z
COM
NC
3.3K
NC
5.6K
EOL 5.6K
TAMPER
8-Zone mode: Nor-
mally closed contact
with 5,6KΩ end-of-
line resistor
4
notE:
Based on the example given, in the event of an alarm, the smoke detector could be reset by turning OFF and ON the PGM output
C1. For more details, please refer to
18.4. turning PGM outputs on and off.