EMR-5000
IM02602012E
Parameter
Description
Setting range
Default
Menu path
WD 1 Alarm
Winding 1 Threshold for Temperature Alarm
Only available if: Device Planning: Alarm Function = Use
0 - 200°C
80°C
[Protection Para
/<1..4>
/Temp-Prot
/RTD
/WD 1]
WD 1 t-Delay
Winding 1 If this time is expired a Temperature Alarm will
be generated.
Only available if: Device Planning: Alarm Function = Use
0 - 360min
1min
[Protection Para
/<1..4>
/Temp-Prot
/RTD
/WD 1]
WD 1 Trip
Winding 1 Threshold for Temperature Trip
Only available if: Device Planning: Trip Function = Use
0 - 200°C
100°C
[Protection Para
/<1..4>
/Temp-Prot
/RTD
/WD 1]
WD 2 Alarm
Function
Winding 2 Alarm Function
Inactive,
Active
Active
[Protection Para
/<1..4>
/Temp-Prot
/RTD
/WD 2]
WD 2 Trip Function Winding 2 Trip Function
Inactive,
Active
Active
[Protection Para
/<1..4>
/Temp-Prot
/RTD
/WD 2]
WD 2 Alarm
Winding 2 Threshold for Temperature Alarm
Only available if: Device Planning: Alarm Function = Use
0 - 200°C
80°C
[Protection Para
/<1..4>
/Temp-Prot
/RTD
/WD 2]
WD 2 t-Delay
Winding 2 If this time is expired a Temperature Alarm will
be generated.
Only available if: Device Planning: Alarm Function = Use
0 - 360min
1min
[Protection Para
/<1..4>
/Temp-Prot
/RTD
/WD 2]