EMR-5000
IM02602012E
AN I02 X - Analog Inputs and Outputs
There are 2 Analog Input and 2 Analog Output channels that are configurable to either 0-20 mA, 4-20 mA, or 0-10 V.
Each of the channels can be independently programmed to either of these three input/output modes.
For details on the Analog Inputs/Outputs, please refer to the Technical Data.
Analog inputs:
- 2 analog inputs with one common potential. Each input has its own common terminal.
- The mode of each input can be individually selected between current or voltage input
- In current mode the measuring range is 0-20 mA
- In current mode the input resistor is 500 Ohm
- In voltage mode the measuring range is 0-10 V
- In voltage mode the input resistor is 100 kOhm
- The accuracy is 0.5 % of the nominal value 20 mA/10 V
- The test voltage of the inputs (one group) against other electrical groups and earth is 2.5 kV
Analog outputs:
- 2 analog outputs with one common potential. Each output has its own common terminal.
- The mode of each output can be individually selected between current or voltage output
- In current mode the output range is 0-20 mA
- In current mode the maximum load resistance is 1 kOhm
- In voltage mode the output range is 0-10 V
- In voltage mode the outputs are short circuit proof
- The accuracy is 0.5 % of the nominal value 20 mA/10 V
- The test voltage of the outputs (one group) against other electrical groups and earth is 2.5 kV
Wiring
- Shielded cable is recommended
- The test voltage against earth is 1.0 kV and against other electrical groups 2.5 kV
HF-Shield
- The terminals of the HF shield should be used, when connecting the shield to earth on both sides of the cable is not
possible. On one side of the cable the shield has to be directly connected to earth.
Make sure that the tightening torque is 0.56-0.79 Nm [5-7 In-lb].
For details on the Analog Inputs or Outputs please refer to the Technical Data.