Hardware Terminals for Zone Interlocking
By means of the zone interlocking terminals, the device can be connected to other Eaton protective devices such as an
FP5000, DT3000, etc.
As an upstream device, the terminals - Phase/Ground IN should be connected to the OUT terminals of up to ten
downstream device(s) by means of a dedicated cable wired in parallel. As a downstream device, the terminals -
Phase/Ground OUT should be connected to the IN terminals of an upstream device by means of a dedicated cable.