EMR-5000
IM02602012E
Parameter
Description
Setting range
Default
Menu path
Count2
Open Counts Allowed #2
Only available if:Bwear Curve Fc = Active
1 - 32000
10000
[Control
/Bkr
/Bwear]
Current3
Interrupted Current Level #3
Only available if:Bwear Curve Fc = Active
0.00 - 2000.00kA
1.15kA
[Control
/Bkr
/Bwear]
Count3
Open Counts Allowed #3
Only available if:Bwear Curve Fc = Active
1 - 32000
10000
[Control
/Bkr
/Bwear]
Current4
Interrupted Current Level #4
Only available if:Bwear Curve Fc = Active
0.00 - 2000.00kA
3.00kA
[Control
/Bkr
/Bwear]
Count4
Open Counts Allowed #4
Only available if:Bwear Curve Fc = Active
1 - 32000
1900
[Control
/Bkr
/Bwear]
Current5
Interrupted Current Level #5
Only available if:Bwear Curve Fc = Active
0.00 - 2000.00kA
5.00kA
[Control
/Bkr
/Bwear]
Count5
Open Counts Allowed #5
Only available if:Bwear Curve Fc = Active
1 - 32000
850
[Control
/Bkr
/Bwear]
Current6
Interrupted Current Level #6
Only available if:Bwear Curve Fc = Active
0.00 - 2000.00kA
6.00kA
[Control
/Bkr
/Bwear]
Count6
Open Counts Allowed #6
Only available if:Bwear Curve Fc = Active
1 - 32000
500
[Control
/Bkr
/Bwear]
Current7
Interrupted Current Level #7
Only available if:Bwear Curve Fc = Active
0.00 - 2000.00kA
13.00kA
[Control
/Bkr
/Bwear]
Count7
Open Counts Allowed #7
Only available if:Bwear Curve Fc = Active
1 - 32000
110
[Control
/Bkr
/Bwear]
www.eaton.com
457