![Eaton EMR-5000 Installation, Operation And Maintenance Manual Download Page 996](http://html1.mh-extra.com/html/eaton/emr-5000/emr-5000_installation-operation-and-maintenance-manual_3985919996.webp)
EMR-5000
IM02602012E
Name
Description
MStart.IOCStartBlock
Signal: Phase Instantaneous Overcurrent Start Delay. IOC (Instantaneous Overcurrent) elements are blocked
for the time programmed under this parameter
MStart.ULoadStartBlock
Signal: Underload Start Delay. Underload(Instantaneous Overcurrent) elements are blocked for the time
programmed under this parameter
MStart.JamStartBlock
Signal: JAM Start Delay. JAM(Instantaneous Overcurrent) elements are blocked for the time programmed
under this parameter
MStart.UnbalStartBlock
Signal: Motor start block current unbalance signal
MStart.Blo-Generic1
Generic Start Delay. This value can be used to block any protective element.1
MStart.Blo-Generic2
Generic Start Delay. This value can be used to block any protective element.2
MStart.Blo-Generic3
Generic Start Delay. This value can be used to block any protective element.3
MStart.Blo-Generic4
Generic Start Delay. This value can be used to block any protective element.4
MStart.Blo-Generic5
Generic Start Delay. This value can be used to block any protective element.5
MStart.I_Transit
Signal: Current transition signal
MStart.T_Transit
Signal: Time transition signal
MStart.MotorStopBlo
Signal: Motor stop block other protection functions
MStart.RFD_IA_Normal
Signal: System IA RotaryFieldDetection Normal
MStart.RFD_IA_Reverse
Signal: System IA RotaryFieldDetection Reverse
MStart.VUnbalStartBlock
Signal: Motor start block voltage unbalance signal.
MStart.UnderVStartBlock
Signal: Undervoltage Start Delay. Undervoltage elements are blocked for the time programmed under this
parameter
MStart.OverVStartBlock
Signal: Overvoltage Start Delay. Overvoltage elements are blocked for the time programmed under this
parameter
MStart.PowerStartBlock
Signal: Power Start Delay. Power elements are blocked for the time programmed under this parameter
MStart.PFacStartBlock
Signal: Power Factor Start Delay. Power Factor elements are blocked for the time programmed under this
parameter
MStart.FrqStartBlock
Signal: Frequency Start Delay. Frequency elements are blocked for the time programmed under this
parameter
MStart.DiffStartBlock
Signal: Differential Start Delay. Differential elements are blocked for the time programmed under this
parameter
MStart.RemStartBlock-I
State of the module input: Remote Motor Start Blocking
MStart.EmgOvr-I
State of the module input: Emergency Override. Signal has to be active in order to release the thermal
capacity of the motor. Please notice that by doing this you run the risk of damaging the motor. “EMGOVR” has
to be set to “DI” or “DI or UI” for this input to take effect
MStart.INSQ-I
State of the module input: INcomplete SeQuence
MStart.ZSS-I
State of the module input: Zero Speed Switch
MStart.STPC Blo-I
State of the module input: With this setting a Digital Input keeps the Motor in the RUN mode, even when the
motor current drops below STPC (motor stop current).
50P[1].Active
Signal: Active
50P[1].ExBlo
Signal: External Blocking
50P[1].Rvs Blo
Signal: Reverse Blocking
50P[1].Blo TripCmd
Signal: Trip Command blocked
www.eaton.com
996