EMR-5000
IM02602012E
Direct Commands of the Modbus
®
Parameter
Description
Setting range
Default
Menu path
Res Diagn Cr
All Modbus Diagnosis Counters will be reset.
Inactive,
Active
Inactive
[Operation
/Reset
/Counter]
Global Protection Parameters of the Modbus
®
Parameter
Description
Setting range
Default
Menu path
Slave ID
Device address (Slave ID) within the bus system. Each
device address has to be unique within a bus system.
Only available if:Device Planning = RTU
1 - 247
1
[Device Para
/Modbus]
Unit ID
The Unit Identifier is used for routing. This parameter is
to be set, if a Modbus RTU and a Modbus TCP network
should be coupled.
Only available if:Device Planning = TCP
1 - 255
255
[Device Para
/Modbus]
TCP Port Config
TCP Port Configuration. This parameter is to be set only
if the default Modubs TCP Port should not be used.
Only available if:Device Planning = TCP
Default,
Private
Default
[Device Para
/Modbus]
Port
Port number
Only available if:Device Planning = TCP And Only
available if: TCP Port Config = Private
502 - 65535
502
[Device Para
/Modbus]
t-timeout
Within this time the answer has to be received by the
Communication system, otherwise the request will be
disregarded. In that case, the Communication system
detects a communication failure and the Communication
System has to send a new request.
Only available if:Device Planning = RTU
0.01 - 10.00s
1s
[Device Para
/Modbus]
Baud rate
Baud rate
Only available if:Device Planning = RTU
1200,
2400,
4800,
9600,
19200,
38400
19200
[Device Para
/Modbus]
www.eaton.com
324