EMR-5000
IM02602012E
Name
Description
Bkr.CES Disturbed
Signal: Command Execution Supervision: Switching Command unsuccessful. Switchgear in disturbed
position.
Bkr.CES Fail TripCmd
Signal: Command Execution Supervision: Command execution failed because trip command is pending.
Bkr.CES SwitchgDir
Signal: Command Execution Supervision respectivly Switching Direction Control: This signal becomes true, if
a switch command is issued even though the switchgear is already in the requested position. Example: A
switchgear that is already OPEN should be switched OPEN again (doubly). The same applies to CLOSE
commands.
Bkr.CES CLOSE d OPEN
Signal: Command Execution Supervision: CLOSE Command during a pending OPEN Command.
Bkr.CES SG not ready
Signal: Command Execution Supervision: Switchgear not ready
Bkr.CES Field Interl
Signal: Command Execution Supervision: Switching Command not executed because of field interlocking.
Bkr.CES SG removed
Signal: Command Execution Supervision: Switching Command unsuccessful, Switchgear removed.
Bkr.TripCmd
Signal: Trip Command
Bkr.Ack TripCmd
Signal: Acknowledge Trip Command
Bkr.Bwear Slow Breaker
Signal: Slow Breaker Alarm
Bkr.Res Bwear Sl Breaker
Signal: Resetting the slow breaker alarm
Bkr.CLOSE Cmd
Signal: CLOSE command issued to the switchgear. Depending on the setting the signal may include the
CLOSE command of the Prot module.
Bkr.OPEN Cmd
Signal: OPEN command issued to the switchgear. Depending on the setting the signal may include the OPEN
command of the Prot module.
Bkr.CLOSE Cmd manual
Signal: CLOSE Cmd manual
Bkr.OPEN Cmd manual
Signal: OPEN Cmd manual
Bkr.CinBkr-52a-I
Module Input State: Feed-back signal of the Bkr (52a)
Bkr.CinBkr-52b-I
Module Input State: Feed-back signal of the Bkr. (52b)
Bkr.Ready-I
Module Input State: Breaker Ready
Bkr.Ack TripCmd-I
State of the module input: Acknowledgment Signal (only for automatic acknowledgment). Module input signal
Bkr.Interl CLOSE1-I
State of the module input: Interlocking of the CLOSE command
Bkr.Interl CLOSE2-I
State of the module input: Interlocking of the CLOSE command
Bkr.Interl CLOSE3-I
State of the module input: Interlocking of the CLOSE command
Bkr.Interl OPEN1-I
State of the module input: Interlocking of the OPEN command
Bkr.Interl OPEN2-I
State of the module input: Interlocking of the OPEN command
Bkr.Interl OPEN3-I
State of the module input: Interlocking of the OPEN command
Bkr.SC CLOSE-I
State of the module input: Switching CLOSE Command, e.g. the state of the Logics or the state of the digital
input
Bkr.SC OPEN-I
State of the module input: Switching OPEN Command, e.g. the state of the Logics or the state of the digital
input
Bkr.Operations Alarm
Signal: Service Alarm, too many Operations
Bkr.Isum Intr trip: IA
Signal: Maximum permissible Summation of the interrupting (tripping) currents exceeded: IA
Bkr.Isum Intr trip: IB
Signal: Maximum permissible Summation of the interrupting (tripping) currents exceeded: IB
Bkr.Isum Intr trip: IC
Signal: Maximum permissible Summation of the interrupting (tripping) currents exceeded: IC
www.eaton.com
994