EMR-5000
IM02602012E
Set-up a Connection Via Ethernet - TCP/IP
Warning: Mixing up IP Addresses
(In case there is more than one protective device within the TCP/IP network or
establishing an unintentional wrong connection to a protective device based on
a wrong entered IP address.
Transferring parameters into the wrong protective device might lead to death,
personal injury, or damage of electrical equipment.
In order to prevent faulty connections, the User MUST document and maintain
a list with the IP addresses of any switchboard/protective devices.
The User MUST double check the IP addresses of the connection
that is to be
established. That means, the User MUST first read out the IP address at the
HMI of the device (within menu [Device para/TCP IP]) then compare the IP
address with the list. If the addresses are identical, establish the
connection. If they are not, DO NOT establish the connection.
Establishing a connection via TCP/IP to the device is only possible if your
device is equipped with an Ethernet Interface (RJ45).
Contact your IT administrator in order to establish the network connection.
Part 1: Set the TCP/IP Parameters at the panel (Device).
Call up the
»Device parameter/TCP/IP« menu at the HMI (panel) and set the following parameters:
TCP/IP address
Subnet mask
Gateway
Part 2: Setting the IP address within PowerPort-E
Call up the menu Settings/Device Connection within PowerPort-E.
Set the radio button Network Connection.
Enter the IP-Address of the device that should be connected.
www.eaton.com