Commissioning Test Description
Set the
JAM
Start delay timer to one second. Set the
JAM
function to “Active” and Threshold to “2 X FLA”. Set the
JAM
“Delay T” to one second. Apply current of “2 X FLA” setting for one second. The relay should not trip. Apply the
same current for 3 seconds. The unit should trip in 2 to 3 seconds.