EMR-5000
IM02602012E
Device Planning Parameters of the BF
Parameter
Description
Options
Default
Menu path
Mode
Mode
Use
Use
[Device Planning]
Global Protection Parameters of the BF
Parameter
Description
Setting range
Default
Menu path
Scheme
Scheme
50BF,
CB Pos,
50BF and CB Pos
50BF
[Protection Para
/Global Prot Para
/Supervision
/BF]
ExBlo1
External blocking of the module, if blocking is activated
(allowed) within a parameter set and if the state of the
assigned signal is true.
1..n, Assignment
List
-.-
[Protection Para
/Global Prot Para
/Supervision
/BF]
ExBlo2
External blocking of the module, if blocking is activated
(allowed) within a parameter set and if the state of the
assigned signal is true.
1..n, Assignment
List
-.-
[Protection Para
/Global Prot Para
/Supervision
/BF]
Trigger
Determining the trigger mode for the Breaker Failure.
- . -,
All Trips,
ExP Fc,
Current Trips
All Trips
[Protection Para
/Global Prot Para
/Supervision
/BF]
Trigger1
Trigger that will start the BF
Trigger
-.-
[Protection Para
/Global Prot Para
/Supervision
/BF]
Trigger2
Trigger that will start the BF
Trigger
-.-
[Protection Para
/Global Prot Para
/Supervision
/BF]