EMR-5000
IM02602012E
Import of the *.SCD File into the Device
When the substation configuration is completed, the *.SCD file has to be transmitted to all connected devices. This has
to be done as follows:
1. Connect the device with your PC/notebook.
2. Start PowerPort E.
3.
Click on »
Receive data from Device«
in the »
Device« menu.
4.
Click on
»
IEC 61850«
in the »
Device Para« menu.
5. Switch the parameter »
IEC 61850 Communication« to »OFF« and submit the changed parameter set into the
device.
6. Click on the IEC icon in the IEC 61850 window.
7. Select the folder where the *.SCD file is stored. Select the *.SCD file and click "Open".
8. A password is requested. Enter the same password, which you use for parameter setting of the device.
9. Following Step 5, again switch on the IEC Communication and submit the changed parameter set into the
device.
10.
Repeat Steps 1 through 9 for all devices connected to this IEC 61850 environment.
11.
If no error message occurs, the configuration has been completed successfully.
•
When changing the substation configuration, usually a new *.SCD file
has to be generated. This *.SCD file must be transmitted to all devices
by means of PowerPort E. If the file is not transmitted to all devices,
IEC 61850 malfunctions will be the result.
•
If the parameters of the devices are changed after the completion of the
substation configuration, changes in the corresponding *.ICD file may
result. This, in turn, may make an update of the *.SCD file necessary.
IEC 61850 Virtual Outputs
In addition to the standardized logical node status information, up to 16 free configurable status information items can
be assigned to the 16 Virtual Outputs. This can be done in the [Device Para/IEC61850] menu.
www.eaton.com
331