EMR-5000
IM02602012E
Parameter
Description
Setting range
Default
Menu path
ThermBlo Fc
ThermBlo Fc
Inactive,
Active
Inactive
[Protection Para
/Global Prot Para
/MStart
/Start Control]
TRN Criteria
Start transition criterion
TRN I,
TRN TIME,
TRN T and I,
TRN T or I
TRN T and I
[Protection Para
/Global Prot Para
/MStart
/Start Control]
TRNT
Motor start transition time limit
Only available if: TRN Criteria = TRN T and I Or TRN
Criteria = TRN TIME
0 - 1200s
10s
[Protection Para
/Global Prot Para
/MStart
/Start Control]
TRNC
Motor start transitions current level in FLA%
Only available if: TRN Criteria = TRN T and I Or TRN
Criteria = TRN I
0.10 - 3.00FLA
1.30FLA
[Protection Para
/Global Prot Para
/MStart
/Start Control]
NOCS
Number of cold starts limit
1 - 5
1
[Protection Para
/Global Prot Para
/MStart
/Start Control]
TBS Fc
Time Between Starts on/off
Inactive,
Active
Inactive
[Protection Para
/Global Prot Para
/MStart
/Start Control]
TBS Timer
Time Between Starts Limit
Only available if: TBS Fc = Active
1 - 240min
60min
[Protection Para
/Global Prot Para
/MStart
/Start Control]
SPH Fc
Starts Per Hour
Inactive,
Active
Inactive
[Protection Para
/Global Prot Para
/MStart
/Start Control]
SPH
SPH
Only available if: SPH Fc = Active
1 - 10
1
[Protection Para
/Global Prot Para
/MStart
/Start Control]
www.eaton.com
492