background image

GENERAL DESCRIPTION

Código
  

code

Tipo

Type

Sensibilidad (A)
   Sensivity

Retardo disparo (s)
   

Tripping delay

P24453 WRU-10 RAL

 0,03-0,1-0,3-0,5-1-3 por ajuste directo/

by direct setting

5-10-30 por/

by

 SETUP

INS-SEL-0,02-0,1-0,2-0,3-0,4-0,5-0,75-1 por ajuste directo / 

by direct setting

3-5-10 por/

by

 SETUP

WRU-10 RAL  Electronic Earth-leakage Protection Relay

Peso 

/ Wheight 

: 168 

REC

RAL

REC

R

REC

               -  DELAY SETTING 

               -  

SETUP ROTATION

                -  ENABLE/DISABLE
                   SELF-RECLOSING SYSTEM 

                -  SENSIVITY SETTING 

                -  outputs contacts SETTING.
                        (LOCKED SIGNAL)  

REC

REC

REC

R

.

  

DESCRIPTION LED AND BUTTONS

Shows  equipment  status  via  a 
display  and  2  LED's.  It  has  5 
button  equipment  setup  and 
setting and 2 button equipment to 
do TEST and RESET.

- SETUP settings

- change PAGES

- GREEN led

: ON 

- RED led, tripped by fault.
- blinking led: pre-alarm

- Reclosures led:
  fix, maximun reclosures
  blinking, betwen reclosures

- RESET Button

- TEST Button

+

REC

PROG

                               Super-inmunized Type A electronic relay. Built-in core balance
                             transformer,   28 mm.Device with self-reclosing system. Symbol         on 
display. It has programmables relays, 3 outputs. Main trip and 2 pre-alarm signals. It has 1  
free voltage input for external ON / OFF. Mounting in DIN rail 46277 (En50022) or PANEL 
72x72 by means of accesories M5ZFF1. Displays setting values and instantaneous earth 
leakage current value (TRMS)  

PRELIMINARY CONSIDERATIONS

CHECKS ON RECEPTION

On receving the instrument, check the following points:
               - The unit’s specifications are the same as those on your order.
               - Check that the device has not suffered any damage during transport.

You can download more information from CIRCUTOR website, www.circutor.es

SAFETY  PRECAUTIONS

The staff using or handling the unit  must follow the common safety measures and warnings included in the 
instruction manual. 

The WRU-10 unit has been specifically designed for its installation in a electric board, enclosure to a DIN 
rail or mounted in panel by means of accesories.  It has a flashing green led (ON) when it is operation and, 
therefore, it shows that there is  voltage and current in the electronic circuit. The user must make sure that 
the equipment is not conected to the power supply at all the times, even when the LED is not flashing.

The user must take into account and observe the informations and warnings included in this instruction 
manual to guarantee the correct operation of the equipment and comply whit the safety specifications. The 
equipment must not turned on until is fully installed in the electrical panel.

Disconnect the equipment from the power supply when the unit´ssafety protection systems are not working 
or there are signs of a problem (in case of visible damage). In this case, contact a qualified technical service 
or with our own technical service (TAS).

INSTALLING THE EQUIPMENT

DIN rail installation. On the inside of the hole must pass all live conductors supplyng electrical energy to   
loads or part of the installation which requires it to earth leakage  protection with this device. In single-phase 
installation (phase and neutral, L and N), three phase - 3 wires (three phases, L1, L2   and L3) or three 
phases - 4 wires (L1, L2, L3 and N). Depending on the level of wiring insulation can be pass through the hole 

2

of    28 mm  (inner diameter)    4-wire 35 mm  of  section,  although it advisable is 25 mm .  All  connections

INSTALLATION AND STAR-UP

¡ IMPORTANT !

!

The unit´s protections systems might not be effective if the unit is used for purpose other  than 
those specifications by the manufacturer.

                

should  be  inside  the  electrical  board.  Please  note  that  with  the  connected  equipment,  terminals  and 
opening covers or removing elements, can give access to dangerous parts to touch. The equipment must 
not be used until it has completely finished installation. The unit must be connected to a power supply circuit 
protected  by  fuses  in  line  with  the  range  and  power  consumption.  In  turn,  the  supply  circuit  must  be 
provided with a circuit breaker or equivalent device to disconnect the equipment from the mains. During the 
wiring cable is advisable a section permitted between 1 - 1.5 mm2. A recommended torque of 0.5-0.6 N.M. 
Cable Stripping Tools length 7 mm.

Power supply                  Operating conditions            Safety

Category III - 300 Vac (En61010)
Double - insulated electric shock protection 
clas II- UL 1053 UL LISTED Certification -
IEC 60755 - IEC 60947-2 Annex M 

Voltage 230 Va.c..
Frequency 50!60 Hz
Burden    4,5 VA

+/- 30%  Temperature -20...70 C

Relative humidity   95%
Max. Altitude 2.000 m
Protection   Ip20

CONNECTIONS BY MEANS OF PLUG-IN CONNECTORS

Rated current:    5  Ac.a.
Rated voltage: 250 Vc.a.   
Rated Load:  1.250 V·A

Rated current: 0,25  Ac.a.
Rated voltage:   230 Vc.a.   
Rated Load:      62,5 V·A

Free voltage, not isolated

Protected by varistor: 
420 Vc.a. - 10 Ac.a.

TERMINAL DESCRIPCIÓN                         FEATURES

1 - 2 EXTERNAL INPUT  TRIP / RECLOSE
     3 PRE-ALARM OUTPUT RELAY, NO
     4 PRE-ALARM OUTPUT RELAY COMMON
     5 LOCKED OUTPUT RELAY, NC
     6 LOCKED OUTPUT RELAY COMMON
     7 SUPPLY 230 Va.c. (Phase or Neutral)
     8 SUPPLY 230 Va.c. (Neutral or Phase)
     9 TRIPPING OUTPUT RELAY, NC
   10 TRIPPING OUTPUT RELAY, NA
   11 TRIPPING OUTPUT RELAY COMMON
   12 WITHOUT USE

Technical Assistance Service  (T.A.S)

If you have any doubts about the running of the equipment or any faults, contact the service staff.

Tel: (+34) 93 745 29 00
Fax: (+34) 93 745 29 14
email: [email protected]

 

 

Vial Sant Jordi s/n
08232 Viladecavalls (Bacelona) SPAIN

RAL

Tripping cause

Mensage  display

Test

Remote signal trip/reclose
Earth leakage fault

TESt
EXT

alue

DIF / v

SAVE
EXIT
OVR

Enter setting values
Exits setting mode

Value reading off scale

Other mesages by display

-  

-  

 

 

 

 

 

 

-  

 

-  BY 
   1.  

.          

   2.  Manual reclose by pushing button 

RESET

.

   3.  
        

 

       

 

(

 

t

I

 and std/+ )

d

d

t

d

 t

d    

      .  

 SAVE.

I

I

.

d

d

- SIGNALLING CONTACTS RELAY STATE,  std/+

 . Select the default position of the relay contacts 

  4-5-6 that indicates the situation of locked by reclosures of the device .  In (Std) 4-6 NO / 4-5 NC 
  and (+) 4-5 NC / 4-6 NO and  appears the symbol in display     

.

- SELF-RECLOSING SYSTEM, REC

. In   reclosure   partial   numbers   by press  

REC

 button we 

  configure the self-reclosing  sequence referred  at  the page which it’s showing us. By default  is 
  configured  nº1 by  earth leakage protection.
          

INDICATION BY LED AND DISPLAY

MAIN TRIP RELAY

LED and display signals a

   change of status by changing from green to red. 
   Display event type  messages or values

PREALARM  SIGNAL.

The LED green is blinking  

   betwen green and red.

BETWEN RECLOSURES.

LED is blinking

LOCKED BY RECLOSURES. 

The yellow LED is  

   fixed. The equipment arrives al maximun number of reclosures established by the self-reclosing 
   sequence. Red display shows the cause.

No OF RECLOSURES.

By short press on the display shows the number of reclosures by earth 

   leakage faults, partial and total number. The partial number are floating pages. In these pages 
   it can configure the self-reclosing sequence by press button.

RECLOSING THE EQUIPMENT.

TRIP LOCKED BY RECLOSURES

Automatic (earth leakage fault or manual). Is           shown on display

External reclose sytem by remote or communications signal. When it forces a trip by remote
signal, only it can reclose by another remote signal. In the case 2 and 3 the partial counters

 of reclosures returns to a zero.

MAIN RELAY PARAMETER SETTING 

SETTING TRIP DELAY

The               message and two values   appear  on the  screen  after 

  pressing  the

button.  The lowest  value indicates  the current set value  and the highest is the 

  values to be configured which are  displayed by pressing

The selected value to be saved  is 

  displayed by showing the message

 

SENSITIVITY SETTING

The same operation as above setting is carried out by pressing 

¡ IMPORTANT !

The relay only self-recloses after a trip by earth leakage current fault. The Test (red button) only verifies the relay trips
the protection. It recloses only by manual pressing RESET button.

   0        
   

1

                      6                                 8, 16, 30, 59, 115 y 224 s                        15 minutes 

   2                    30                                 20, 40 s y 5 min. to the end.                    15 minutes
   3                      8                                 30 s, 1, 2, 3, 4, 5, 6 y 7 min                     15 minutes
   4                      6                                 10, 20, 30, 60, 130 y 600 s                      15 minutes
   5                      6                                 2, 4 y 8 min. to the end.                           15 minutes
   6                      7                                 30 s, 1, 2, 3, 4, 8 y 16 min                       30 minutes
   7                    10                                 1 min                                                        30 minutes
   8                    10                                 90 s                                                          30 minutes
   9                      8                                 2, 4 y 6 min. To the end.                          15 minutes
 10                    10                                 3 min                                                        30 minutes
 11                      7                                 2, 4, 8, 16, 32, 32 y 32 min                      15 minutes

                                                              DISABLED

 12                    31                                 2, 4 y 6 min. to the end.                           60 minutes
 13                      3                                 2, 4 y 8 min                                              15 minutes
 14                     

...                                  ...                                                                ...

SREC      No RECLOSURES                      TIME SEQUENCES                             RESET TIME

PROG

With the

button  the submenus are browsed 

and with the       button the  values to  be selected 
are displayed

to  enter  the value. The  equipment 

configures the  value by  displaying

on the 

display and then exits Setting Mode If  the   keypad 
remains  inactive for a certain time, the   equipment   
automatically  exits    Setting  Mode  and  displays

 

 

.

 
Press  

  

 “

SAVE

” 

 

PROG

PROG

SETUP

 SETTINGS

FREC

LIM

ALAR

RSTC

Button 

PROG

   50 Hz
   60 Hz

10 s, 30 A

I

d

t

d

SP

   Pre-alarm current %

   Delay pre-alarma seg.

   Contact NO/NC

AU     Reconectable

1 s,   3 A

OFF
  50
  60
  70
  80
MAIN
0,02
 0,1
 0,2
 0,3
 0,4
0,75
   1
   3
  NO
YES
AUTO
MANU
  NO
 YES

Button

FREQ

(

50

) frecuency (Hz)

LIM

,(

1s, 3A

), range of values (Id / td)

- ALAR

, pre-alarm.

     . Id ( 

OFF

), It’is not pre-alarm.

     . Td ( 

20 ms

), time.

     . SP (

NO

),contact states. 

                     3-4 [

NA

/NC]

     .AU (

AutO

), Relay reclaim the state.

RSTC

, (

NO

), Reset the partial reclosures.

Default values in 

SETUP

M98229001-03-14A

Reviews: