![Eaton EMR-5000 Installation, Operation And Maintenance Manual Download Page 986](http://html1.mh-extra.com/html/eaton/emr-5000/emr-5000_installation-operation-and-maintenance-manual_3985919986.webp)
EMR-5000
IM02602012E
www.eaton.com
986
t [s]
t-multiplier
x * Pickup
(Multiples of Pickup)
t =
0.0515
*t-multiplier [s]
Pickup
-1
IG
( )
0.02
+ 0.1140
( )
t =
4.85
*t-multiplier [s]
-1
IG
( )
2
Pickup
Trip
Reset
Notice!
Various Reset Modes are available . Resetting via characteristic, delayed, and
instantaneous .
ANSI MINV