Parameter
Description
Setting range
Default
Menu path
WD 2 Trip
Winding 2 Threshold for Temperature Trip
Only available if: Device Planning: Trip Function = Use
0 - 200°C
100°C
[Protection Para
/<1..4>
/Temp-Prot
/RTD
/WD 2]
WD 3 Alarm
Function
Winding 3 Alarm Function
Inactive,
Active
Active
[Protection Para
/<1..4>
/Temp-Prot
/RTD
/WD 3]
WD 3 Trip Function Winding 3 Trip Function
Inactive,
Active
Active
[Protection Para
/<1..4>
/Temp-Prot
/RTD
/WD 3]
WD 3 Alarm
Winding 3 Threshold for Temperature Alarm
Only available if: Device Planning: Alarm Function = Use
0 - 200°C
80°C
[Protection Para
/<1..4>
/Temp-Prot
/RTD
/WD 3]
WD 3 t-Delay
Winding 3 If this time is expired a Temperature Alarm will
be generated.
Only available if: Device Planning: Alarm Function = Use
0 - 360min
1min
[Protection Para
/<1..4>
/Temp-Prot
/RTD
/WD 3]
WD 3 Trip
Winding 3 Threshold for Temperature Trip
Only available if: Device Planning: Trip Function = Use
0 - 200°C
100°C
[Protection Para
/<1..4>
/Temp-Prot
/RTD
/WD 3]
WD 4 Alarm
Function
Winding 4 Alarm Function
Inactive,
Active
Active
[Protection Para
/<1..4>
/Temp-Prot
/RTD
/WD 4]