Setting Group Parameters of the Load Shedding
Parameter
Description
Setting range
Default
Menu path
Function
Permanent activation or deactivation of module/element. Inactive,
Active
Inactive
[Protection Para
/<1..4>
/MLS]
ExBlo Fc
Activate (allow) or inactivate (disallow) blocking of the
module/element. This parameter is only effective if a
signal is assigned to the corresponding global protection
parameter. If the signal becomes true, those
modules/elements are blocked that are parameterized
"ExBlo Fc=active".
Inactive,
Active
Inactive
[Protection Para
/<1..4>
/MLS]
Pickup Threshold
Load shedding pickup current as multiplier of FLA
0.50 - 1.50FLA
0.90FLA
[Protection Para
/<1..4>
/MLS]
t-Pickup Delay
Trip delay time
0.0 - 5.0s
1.0s
[Protection Para
/<1..4>
/MLS]
Dropout Threshold
Load shedding dropout as multiplier of FLA (Hysteresis)
0.50 - 1.50FLA
0.50FLA
[Protection Para
/<1..4>
/MLS]
t-Drop Delay
Dropout delay time
0.0 - 5.0s
1.0s
[Protection Para
/<1..4>
/MLS]