EMR-5000
IM02602012E
Name
Description
49.I2T Remained
Thermal capacity remained.
URTD.WD1
Winding 1
URTD.WD2
Winding 2
URTD.WD3
Winding 3
URTD.WD4
Winding 4
URTD.WD5
Winding 5
URTD.WD6
Winding 6
URTD.MB1
Motor Bearing 1
URTD.MB2
Motor Bearing 2
URTD.LB1
Load Bearing 1
URTD.LB2
Load Bearing 2
URTD.Aux1
Auxiliary1
URTD.Aux2
Auxiliary2
URTD.RTD Max
Maximum temperature of all channels.
RTD.Hottest WD
Hottest motor winding temperature in degrees C.
RTD.Hottest MB
Hottest motor bearing temperature in degrees C. Resettable with "Sys Res OperationsCr" or "All".
ECr.Syst VA RMS
Measured VAs (RMS)
ECr.Syst W RMS
Measured Watts. Active power (P- = Fed Active Power, P+ = Consumpted Active Power) (RMS)
ECr.Syst VAr Fund.
Measured VARs. Reactive power (Q- = Fed Reactive Power, Q+ = Consumpted Reactive Power)
(Fundamental)
ECr.Apt PF
Measured Value (Calculated): 55A - Apparent Power Factor
ECr.Disp PF
Measured Value (Calculated): 55D - Displacement Power Factor
ECr.VAh Net
Net VA Hours
ECr.Wh Net
Net Watt Hours
ECr.Wh Fwd
Positive Active Power is consumed active energy
ECr.Wh Rev
Negative Active Power (Fed Energy)
ECr.VArh Net
Net VAr Hours
ECr.VArh Lag
Positive Reactive Power is consumed Reactive Energy
ECr.VArh Lead
Negative Reactive Power (Fed Energy)