EMR-5000
IM02602012E
Global Protection Parameters of the Analog Outputs
Parameter
Description
Setting range
Default
Menu path
Assignment
Assignment
1..n,
AnalogOutputList
-.-
[Device Para
/Analog Outputs
/AnOut[1]]
Range
Adjustable range
0...20mA,
4...20mA,
0...10V
0...20mA
[Device Para
/Analog Outputs
/AnOut[1]]
Range max
Adjustable range maximum.
-999999.00 -
999999.00°C
1.00°C
[Device Para
/Analog Outputs
/AnOut[1]]
Range min
Adjustable range minimum.
-999999.00 -
999999.00°C
0.00°C
[Device Para
/Analog Outputs
/AnOut[1]]
Force Mode
For commissioning purposes or for maintanance, Analog
Outputs can be set by force. By means of this function
the normal Analog Outputs can be overwritten (forced).
Permanent,
Timeout
Permanent
[Service
/Test Mode (Prot
inhibit)
/WARNING! Cont?
/Analog Outputs
/AnOut[1]]
t-Timeout Force
The Analog Output Value will be set by force for the
duration of this time. That means for the duration of this
time the Analog Output does not show the value of the
signals that are assigned on it.
Only available if: Force Mode = Active
0.00 - 300.00s
0.03s
[Service
/Test Mode (Prot
inhibit)
/WARNING! Cont?
/Analog Outputs
/AnOut[1]]
www.eaton.com
126