EMR-5000
IM02602012E
Measuring Elements
AnIn[1] ,AnIn[2]
Signals (Output States) of the Analog Measuring Elements
Signal
Description
Broken wire
Signal: Broken wire. This signal is only valid, if the analog input is used in the 4..20 mA mode.
Input forced
The value of analog Input has been set by force. That means that the value of the analog Input is
forced and does not represent the real measured value.
Direct Commands of the Analog Measuring Elements
Parameter
Description
Setting range
Default
Menu path
Function
Permanent activation or deactivation of module/element. Inactive,
Active
Inactive
[Service
/Test Mode (Prot
inhibit)
/WARNING! Cont?
/Analog Inputs
/AnIn[1]]
Force Value
By means of this function the Analog Input Value can be
overwritten (forced).
0.0 - 100.0%
0%
[Service
/Test Mode (Prot
inhibit)
/WARNING! Cont?
/Analog Inputs
/AnIn[1]]
www.eaton.com
135