Global Protection Parameter of the Demand Management
Parameter
Description
Setting range
Default
Menu path
Function
Permanent activation or deactivation of module/element. Inactive,
Active
Inactive
[SysA
/General Settings]
ExBlo Fc
Activate (allow) or inactivate (disallow) blocking of the
module/element. This parameter is only effective if a
signal is assigned to the corresponding global protection
parameter. If the signal becomes true, those
modules/elements are blocked that are parameterized
"ExBlo Fc=active".
1..n, Assignment
List
-.-
[SysA
/General Settings]
Alarm
Alarm
Inactive,
Active
Inactive
[SysA
/Power
/Watt]
Threshold
Threshold (to be entered as primary value)
1 - 40000000kW
10000kW
[SysA
/Power
/Watt]
t-Delay
Tripping Delay
0 - 60min
0min
[SysA
/Power
/Watt]
Alarm
Alarm
Inactive,
Active
Inactive
[SysA
/Power
/VAr]
Threshold
Threshold (to be entered as primary value)
1 - 40000000kVAr
10000kVAr
[SysA
/Power
/VAr]
t-Delay
Tripping Delay
0 - 60min
0min
[SysA
/Power
/VAr]
Alarm
Alarm
Inactive,
Active
Inactive
[SysA
/Power
/VA]