EMR-5000
IM02602012E
Testing the dropout ratio of %(V2/V1)
Having tripped the relay in the previous test, now decrease the phase A voltage. The dropout of »
%(V2/V1)« has to be
1% below the »
%(V2/V1)«setting.
Successful test result:
The measured trip delays, threshold values, and dropout ratios are within the permitted deviations/tolerances, specified
under Technical Data.