background image

 

 
 

Broyce Control Ltd., Pool Street, Wolverhampton, West Midlands WV2 4HN. England 

Tel: +44 (0) 1902 773746 Fax: +44 (0) 1902 420639 Email: [email protected] Web: www.broycecontrol.com 

                   The Information provided in this literature is believed to be accurate (subject to change without prior notice); however, use of such information shall be entirely at the user’s own risk.

 

 

P50EFR-4-A.DOCX 

Page 

1

 of 

1806 

 

 

 

  

 

 

  

 

 

 
 

 
 

 

 

 

 

                                                                                                                                                                                                                                                          
 
 
 
 
 
 
 

 

 
 
 
 

 

 

 

FUNCTION DIAGRAM 

 

 

 

 

 

Terminal Protection 
to IP20 

 

 

 

Panel (Flush) Mount enclosure 

 

Adjustable side clips provide quick method of mounting (no fixing screws required) 

 

2 models available (SPDT or 2 x N.O. relay outputs)

 

 

Adjustable Trip current setting  (0.1 – 2A) 

 

Adjustable Definite Time setting  (0.05 – 1s) 

 

True RMS 

 

Separate “Test” and “Reset” push buttons 

 

Relay energises when fault exceeds set trip threshold 

 

LED indication for Power Supply and Trip status 

 

SPDT relay output - 8A 

(Part No. P50EFR)

 

 

2 x N.O. relay outputs - 3A 

(Part No. P50EFR/2)

 

 

Single supply voltage option – 115V or 230V AC 

 

Type: P50EFR & P50EFR/2 

Earth Fault Relay (Definite Time – DT)

 

 

INSTALLATION AND SETTING 

 

 
 

 

BEFORE INSTALLATION, ISOLATE THE SUPPLY. 

 

Remove the P50EFR from the packaging. 

 

Lift the raised part of the side clip and slide towards the rear of the 
housing to remove. Carry this out on both sides. 

 

Insert the P50EFR in to the panel cut-out and fit the side clips back 
on to the housing. 

 

Slide the clips towards the front of the unit until they come in to 
contact with the reverse side of the panel. The unit is now secured 
in place. 

 

Connect the wires to the rear terminals as required following the 
diagram shown on the next page and for the relevant model shown.  

 

Ensure the Auxiliary supply voltage to be connected to terminals 1 
and 8 matches the rating of the product.  

 

Setting up 

 

The unit should be set according to the requirements of the 
application. 

 

 

Applying power 

 

Apply power and the green “Power on” 

 LED will illuminate. 

 

Assuming no fault present, the output relay(s) will remain in the de-
energised state.  

 

If a fault is detected, the red LED 

 will remain constantly lit for the 

set delay “t”. If the unit trips, the red LED will then flash.  

 

Fault simulation (Test mode) 

 

The unit can be placed into a fault condition by pressing the “Test” 
button 

 on the front of the unit. The output relay(s) will energise.  

 

Press the “Reset” button 

 on the front to reset the unit. The 

output relay(s) revert back to the de-energised state. 

 

The unit can also be reset by interrupting the power supply. 

 

To satisfy regulations, it is recommended that the device be tested 
periodically to ensure correct operation.  

 

Troubleshooting 

 

If the unit fails to operate correctly check that all wiring and 
connections are good.  

 

 

 

 

SETTING DETAILS  

 

 
 
 
 
 
 
 

 

 

 

 

1. “Trip current Io>” (Current setting) adjustment  4. Green “Power On” (Normal) LED indication 
2. “Time delay” (Operating time) adjustment 

5. Red “Tripped” LED indication 

3. “TEST” button 

 

 

 

6. “RESET” button 

 

 

 

 

 

 

Reviews: