True R.M.S. measurements 

 

Adjustable Low-set tripping threshold 

 

Adjustable High-set tripping threshold with option to disable 

 

Adjustable Time Multiplier for defining curve tripping characteristic (applicable to Low-set triggering only) 

 

Instantaneous tripping on High-set triggering 

 

Test and Reset button for simulating and clearing of fault condition 

 

Red LED indication of Low-set or High-set triggering and tripping 

 

Green LED indication for Auxiliary power supply presence 

 

Microprocessor based (self checking) with non-volatile memory 

 

Terminals suitable for 2 x 2.5mm

2

 wires (complete with protective cover) 

 
 
      

 

  
  
 
                                                                                                                                                                                                                                                                                                             
 
 
 

 
 
 
 
 

 

 
 
 
 
 
 
 
 
 
 
 
 

 

GENERAL OVERVIEW 

 
The P9630 (from the P9600 series family of IDMT/DT relays) is a microprocessor based relay 
designed to monitor and detect Overcurrents in 3-phase applications. Typically the P9630 is 
wired in conjunction with external current transformers (1 per phase) of the feeder to be 
protected. 
 
The adjustments and indicators are laid out such to help the user during set-up and fault 
finding. The adjustment for the Low

Low

Low

Low----set

set

set

set for example has its corresponding red LED positioned 

above it so it is clear to which function this LED relates to. The same also applies to the High

High

High

High----

set

set

set

set adjustment and LED. Adjustment and LED operation is explained further on the next page. 
 
The adjustment for IDT 

IDT 

IDT 

IDT (which defines the curve response to tripping)    is assigned to the Low

Low

Low

Low----

set

set

set

set triggering only. The High

High

High

High----set

set

set

set does not have any additional adjustments and hence will trip 

instantaneously if triggered. If required, the High

High

High

High----set

set

set

set can be set to disabled. 

 
A Test mode is provided (also accessible with the tamperproof transparent cover closed) to 
confirm the correct operation of the internal relay. The relay will energise when the “TEST”

“TEST”

“TEST”

“TEST” 

button is pressed and de-energise when the “RESET”

“RESET”

“RESET”

“RESET” button is pressed. 

 
 
 
 

 

 
 
 
 
 

 
 
 

 

 
    

 

 

OPERATION 

 

Example 1. 

 

  When an Overcurrent occurs in one of the phases and the level of 
current exceeds the “L

“L

“L

“Low

ow

ow

ow----set

set

set

set I>”

 I>”

 I>”

 I>” trip threshold, the corresponding 

red LED above the adjustment illuminates. The time out then 
commences however the point at which tripping occurs is defined by: 

 

A, the level of current that is above the trip threshold. 
B, the Time Multiplier setting. 

 

When tripping finally occurs, the red LED will then flash indicating a 

tripped condition. 
 
  If the fault current has been removed, pressing the “RESET” 

 “RESET” 

 “RESET” 

 “RESET” button 

will return the relay back to normal operation. The red LED will then 
extinguish. 
 
Example 2. 

 

If a fault current occurs such that it exceeds the “High

“High

“High

“High----set I

set I

set I

set I>>”

>>”

>>”

>>” trip 

threshold the relay will de-energise with no delay. The red LED above 
the “High

“High

“High

“High----set I

set I

set I

set I>>”

>>”

>>”

>>” adjustment will flash. 

 

In the event of an Overcurrent condition, the basic sequence of 
events is shown below. 

Assuming High-set trip is enabled.

 

    
    
    
    
    
    
    
    
    
    
    
    
    
    
    
    
    

 

PRESENTATION

 

 

 

 
 

 

    

    

    

    
    
    
    
    

 

  

 

    
    
    
    
    
    
    
    
    
    
    
    
    
    

1.  

“Time Multiplier”

 adjustment*                     5. 

“Low-set triggered” 

red LED indication 

2. 

“Low-set I>”

 trip adjustment*                      6. 

“High-set triggered” 

red LED indication 

3. 

“High-set I>>”

 trip adjustment*                   7. 

“TEST”

 button   

4. 

“Power supply”

 green LED indication               8. 

“RESET”

 button       

                                                      * accessible only when the front cover is open 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

START 

OVERCURRENT

occurs 

Low-set I> 

triggered

 

Time out 

commences 

High-set 

I>> 

triggered? 

TRIP! 

 
 

Timeout 

complete? 

‰

 

 

Dims: 

W x H. 96 x 96mm (front) 

W x H. 89.5 x 89.5mm (main body) 

L. 107mm 

 

 