5
Categories and Use of Basic Application Instructions
DVP-PM Application Manual
5-83
Adjust the D/A conversion curve of DVP02DA-H2. Set the OFFSET value of CH2 as 0mA ( =
K0
LSB
) and GAIN value
as 10mA
(
= K1,000
LSB
).
M1002
TO
K1
K1
H18
K1
TO
K1
K33
H0
K1
X0
TO
K1
K22
K0
K1
TO
K1
K28
K1000
K1
1. Write H’18 into CR#1 of analog output module No. 1 to set CH2 as mode 3 (current output: 0mA ~ +20mA).
2. Write H’0 into CR#33 to allow OFFSET/GAIN tuning in CH1 and CH2.
3. When X0 goes from OFF to ON, write the OFFSET value K0
LSB
into CR#22 and the GAIN value K1,000
LSB
into
CR#28.
FROM/TO Application Example 4:
Adjust the D/A conversion curve of DVP02DA-H2. Set the OFFSET value of CH2 as 2mA ( = K400
LSB
) and GAIN
value as 18mA ( = K3,600
LSB
)
.
M1002
TO
K1
K1
H10
K1
TO
K1
K33
H0
K1
X0
TO
K1
K23
K400
K1
TO
K1
K29
K3600
K1
1. Write H’10 to CR#1 of analog output module No. 1 to set CH2 as mode 2 (current output: +4mA ~ +20mA).
2. Write H’0 to CR#33 to allow OFFSET/GAIN tuning in CH1 and CH2.
3. When X0 goes from OFF to ON, write the OFFSET value K400
LSB
into CR#23 and GAIN value K3,600
LSB
into
CR#29.
Summary of Contents for DVP-10PM
Page 1: ......
Page 45: ...2 Hardware Specifications and Wiring DVP PM Application Manual 2 30 MEMO...
Page 125: ...3 Functions of Devices in DVP PM DVP PM Application Manual 3 80 MEMO...
Page 341: ...8 Application Examples DVP PM Application Manual 8 2 Trajectory 3 Trajectory 4...
Page 427: ...9 Electrical CAM DVP PM Application Manual 9 74...
Page 437: ...10 Encrypting User Program DVP PM Application Manual 10 10 MEMO...
Page 458: ...11 G code Application DVP PM Application Manual 11 21 B O100 main program...
Page 561: ...14 Appendix DVP PM Application Manual 14 4 MEMO...