15
Appendix
DVP-PM Application Manual
14-1
15.1 Appendix A: Error Codes
If error occurs in O100 or OX program area in DVP-PM, the error flag will be ON and ERROR indicator will flash. The
causes of errors could be illegal use of instruction operand (device), program syntax error, or improper setting of
motion subroutine patameters. Users can monitor the error register and obtain the cause of error according to the
error code in error registertrs.
Error codes in all program areas and motion axes & devices for displaying steps
Program area
O100
OX
Motion error
Motion error
Error type
Program
error
X axis
Y axis
Z axis
Program
error
X axis
Y axis
Z axis
Error flag
M1953 M1793 M1873
M2033
M1793 M1793 M1873
M2033
Error register
D1802 D1857 D1937
D2017
D1857 D1857
D1937
D2017
Number of
error step
D1803 D1869
D1869 D1869
Error codes for program area and motion axis (in hex)
Code
Cause
Code
Cause
0002
No content in the applied subroutine
0031
Forward pulses prohibited
0003
No corresponding Pn for CJ, CJN, JMP
0032
Reverse pulses prohibited
0004
There is a subroutine flag in main program
0033
Left/right limit achieved
0005
No subroutine
0040
Incorrect use range of device
0006
Repeated index in the same program
0041
MODRD and MODWR communication
time-out
0007
Repeated subroutine index
0044
V/Z modification error
0008
Repeated index of jump instructions in
different subroutines
0045
Floating point conversion error
0009
JMP instruction and CALL instruction are
using the same flag.
0E18
BCD conversion error
000A
The index is the same as subroutine index
0E19
Arithmetic error in division (divisor = 0)
0011
Incorrect target position (I) setting
C401
General loop error
0012
Incorrect target position (II) setting
C402
Continuous use of LD/LDI for more than 9
times
0021
Incorrect running speed (I) setting
C404
RPT ~ RPE are used more than 1 layer
0022
Incorrect running speed (II) setting
C405
SRET is used between RPT ~ RPE
0023
Incorrect zero return speed (V
RT
) setting
C4EE
There is no end instruction (M102, M2) in the
program
0024
Incorrect zerp return deceleration speed
(V
CR
) setting
C4FF
No such instruction / Incorrect operand
format or incorrect range
0025
Incorrect JOG speed setting
Summary of Contents for DVP-10PM
Page 1: ......
Page 45: ...2 Hardware Specifications and Wiring DVP PM Application Manual 2 30 MEMO...
Page 125: ...3 Functions of Devices in DVP PM DVP PM Application Manual 3 80 MEMO...
Page 341: ...8 Application Examples DVP PM Application Manual 8 2 Trajectory 3 Trajectory 4...
Page 427: ...9 Electrical CAM DVP PM Application Manual 9 74...
Page 437: ...10 Encrypting User Program DVP PM Application Manual 10 10 MEMO...
Page 458: ...11 G code Application DVP PM Application Manual 11 21 B O100 main program...
Page 561: ...14 Appendix DVP PM Application Manual 14 4 MEMO...