
MCO 305 Design Guide
__ Parameter Reference __
¾
default setting
[ ]
value for use in communication via serial communication port
208
MG.33.L4.02 – VLT
®
is a registered Danfoss trademark
33-59 Terminal X57/10 Digital Input
I_FUNCTION_10
¾
No function
[0]
Function
Defines function of digital input 10 of MCO 305.
33-60 Terminal X59/1 and X59/2 Mode
IOMODE
Option
Input
X59/1 = Input 11
X59/2 = Input 12
[0]
¾
Output
X59/1 = Output 1
X59/2 = Output 2
[1]
Function
Two of the terminals (X59/1 and X59/2) can be
configured as digital input or digital output.
33-61 Terminal X59/1 Digital Input
I_FUNCTION_11
¾
No function
[0]
Function
Defines function of digital input 11 of MCO 305.
NOTE: This parameter is only visible when p. 33-60
IOMODE = [0], i.e. input_11 is used in standard
mode.
33-62 Terminal X59/2 Digital Input
I_FUNCTION_12
¾
No function
[0]
Function
Defines function of digital input 12 of MCO 305.
NOTE: This parameter is only visible when p. 33-60
IOMODE = 0, i.e. input 12 is used in standard
mode.
Digital Output Functions
Digital output function
Select
Terminal
¾
No
function
[0]
X59
Moving 'no'
[1] X59
Moving 'nc'
[2] X59
Error 'no'
[3] X59
Error 'nc'
[4] X59
Brake control 'no'
[5] X59
Brake control 'nc'
[6]
X59
NOTE: 8 outputs are only available if par. 33-60
IOMODE is set to [1].
You can program all digital outputs 1 – 8 (6) to
these functions:
No function [0]:
No reaction on signals from
the output_n.
Moving no [1]:
Defines digital output_n of the
MCO 305 for motion command active. The output
is always activated (24 V) as soon as a motion
command is active, regardless in which mode
(position, velocity or synchronization command).
This function is not suitable for monitoring the
motor, since the motor could be standing still
although the control is in motion.
Moving nc [2]:
Defines digital output_n for
motion command active. The output is always
activated (0 V) as soon as a motion command is
active, regardless in which mode (position,
velocity or synchronization command).
This function is not suitable for monitoring the
motor, since the motor could be standing still
although the control is in motion.
Error no [3]:
Defines output_n for error. The
output is set (24 V) when an error has occurred.
When the error is cleared this output is re-set.
NB!:
The setting of this parameter does not
influence the use of the OUT and OUTB
commands. With these commands it is
also possible to change the outputs which have
pre-defined functions.
Error nc [4]:
Defines output_n for error. The
output is set (0 V) when an error has occurred.
When the error is cleared this output is re-set.
NB!:
The setting of this parameter does not
influence the use of the OUT and OUTB
commands. With these commands it is
also possible to change the outputs which have
pre-defined functions.
Summary of Contents for MCO 305
Page 4: ......