MCO 305 Design Guide
__ Software Reference __
MG.33.L4.02 – VLT
®
is a registered Danfoss trademark
139
OUT
Summary
Set or re-set digital outputs.
Syntax
OUT n s
or
OUT X/n s
Parameter
n = output number
MCO 305: 1 – 8 (6)
FC 312 outputs: 27
Relay outputs: 21 (relay 1) and 22 (relay 2), Note: FC 312 < 11 kW
only has relay 1.
MCB 105, relay outputs: X34/1 (relay 7), X34/5 (relay 8) and X34/10
(relay 9).
X/n = terminal block / pin number
s = condition
0 = OFF
1 = ON
Description
The 8 (6) digital outputs of the MCO 305 option, the digital and relay outputs of
FC 300, and the relay outputs of MCB 105 can be set and re-set by using the OUT
command.
The selection of the mode for output 7,8 is done by par. 33-60 IOMODE.
If the outputs are used NPN or PNP depends on the selection for the standard
FC 300 outputs set in par. 5-00.
NB!:
If an illegal combination or a pin number is used for X/n, which can not be set,
then error 171 will be reported.
But there is no check if an input is used instead of an output or vice versa.
NB!:
After switching on the system, all outputs are OFF.
These outputs, which have pre-defined functions according to the I/O parameter
settings, will also be influenced by the OUT commands!
The actual output status remains as it is, even after program end or program
abort.
The output circuit and maximum load current can be taken from MCO Operating
Instructions and the FC 300 Operating Instructions.
Command Group
I/O
Cross Index
OUTB, IN, INB,
Parameters: 33-60
Terminal X59/1 and X59/2 Mode
, IOMODE, 33-63...70
Terminal
X59/n Digital Output
, O_FUNCTION_n
Syntax Example
OUT 3 1
// set output 3 on MCO 305 to 1
OUT 27 1
// set output 27 on FC 300 main board to 1
OUT X59/3 1
// set output 3 on MCO 305 to 1
OUT X34/1 1
// set first relay on relay option (relay 7) to 1
Program Sample
OUT_01.M