Si21-205
Troubleshooting for Outdoor Unit (25/35 class)
Troubleshooting
185
Troubleshooting
Check No.4
Refer to P.187
Check No.6
Refer to P.189
Check No.7
Refer to P.190
Check No.9
Refer to P.191
(R2855)
Caution
Be sure to turn off power switch before connect or disconnect connector,
or parts damage may be occurred.
Replace the fan motor.
Repair the connector or fan
motor lead wires.
Replace the heat exchanger
thermistor.
Replace PCB.
Replace the electronic
expansion valve or coil.
Replace the PCB.
Change the air outlet grille
position.
Change the installation
location.
Clean the heat exchanger.
Check the installation space.
Check No.9
Outdoor fan check
Judgment
Check No.6
Heat exchanger thermistor check
Judgment
Check No.7
Installation condition
check
Check No.4
Electronic expansion valve check
Abnormal
Normal
Normal
Normal
Normal
Abnormal
Abnormal
Abnormal
Summary of Contents for Sky Air B-Series R-410A
Page 7: ...Si21 205 vi Table of Contents ...
Page 15: ...Models Si21 205 4 Model Name and Power Supply ...
Page 16: ...Si21 205 Functions 5 Part 2 Functions 1 List of Functions 6 ...
Page 35: ...Wireless Remote Controller Si21 205 24 Remote Controller ...
Page 79: ...Settings Concerning Maintenance Si21 205 68 Field Setting Detail of PCB 2 ...
Page 83: ...Maintenance Mode Setting Si21 205 72 Field Setting ...
Page 239: ...Troubleshooting for Outdoor Unit 50 60 class Si21 205 228 Troubleshooting ...
Page 321: ...Outdoor Unit 50 60 class Si21 205 310 Removal Procedure ...