Outdoor Unit (50/60 class)
Si21-205
308
Removal Procedure
4.8
Removal of the Compressor
Procedure
Warning
Be sure to wait 10 minutes or more after turning off all power supplies
before disassembling work.
Step
Procedure
Points
1
Remove the terminal
cover.
2
Disconnect the lead
wires of the
compressor.
Be careful so as not to burn
the compressor terminals or
the name plate.
Make a note.
U : red
V : yellow
W : blue
N : brown
N
W
U
V