Si21-205
Field Piping and Wiring
Field Piping and Wiring
39
Caution
Drain piping connections
Do not connect the drain piping directly to sewage pipes that smell of ammonia. The ammonia
in the sewage might enter the indoor unit through the drain pipes and corrode the heat
exchanger.
Keep in mind that it will become the cause of getting drain pipe blocked if water collects on
drain pipe
Drain pipe
Service drain outlet (with rubber plug)
(Use this outlet to drain water from
the drain pan)
Plastic container
for pouring
(Tube should be
about 100 mm long.)
100
<Adding water through air outlet>
[Method of adding water]
Fig. 23
(mm)
1
2
3
Single phase
power supply
(50Hz 220-240V)
No.1 No.2
No.3
Power supply
terminal block
Fig. 24
Control
box lid
Remove the
control box lid
(take off 2 screws)