Indoor Unit
Si21-205
84
Function and Control
Mode Conflict
[Overview]
While the indoor unit for another room and the outdoor unit are operating, when the indoor unit
for the own room is activated, the operation mode which can be selected in the own room has
some restrictions as mentioned below.
i)
In case an priority for operation mode selection is given to the own room by setting the dip
switch of outdoor unit;
→
The own room can be operated in any mode.
ii)
In case an priority for operation mode selection is not given to the own room by setting the
dip switch of outdoor unit;
→
The unit can be operated as follows:
:Operational
∗:
The unit for another room is switched into non-operational condition.
×
: Non-operational
* Operation of the indoor unit for the own room during non-operation.
•
Fan = OFF
•
Louver = becomes horizontal position.
•
ON LED on the remote controller = blinks.
•
Indication of "under central control" on the remote controller = displayed.
Note): During automatic operation, at the time of changing operation mode to Automatic cooling
or Automatic heating, the unit is operated as the table shown above.
Outdoor unit
operation mode
when an operation
mode for the own
room is selected.
(The outdoor unit
is operated in the
mode as
mentioned below.)
Operation mode selected in the own room
Cooling or
Automatic cooling
(Note)
Dry
Blowing
Heating or
Automatic heating
(Note)
Cooling
×
Heating
×
×
×
Blowing
∗
Summary of Contents for Sky Air B-Series R-410A
Page 7: ...Si21 205 vi Table of Contents ...
Page 15: ...Models Si21 205 4 Model Name and Power Supply ...
Page 16: ...Si21 205 Functions 5 Part 2 Functions 1 List of Functions 6 ...
Page 35: ...Wireless Remote Controller Si21 205 24 Remote Controller ...
Page 79: ...Settings Concerning Maintenance Si21 205 68 Field Setting Detail of PCB 2 ...
Page 83: ...Maintenance Mode Setting Si21 205 72 Field Setting ...
Page 239: ...Troubleshooting for Outdoor Unit 50 60 class Si21 205 228 Troubleshooting ...
Page 321: ...Outdoor Unit 50 60 class Si21 205 310 Removal Procedure ...