4. Error Codes and LED Indication
Symbols
5
: Blinks
4
: On
3
: Off — : No connection with troubleshooting
: High probability of malfunction
: Possibility of malfunction
: Low probability of malfunction
— : No possibility of malfunction (do not replace)
System
Remote
Controller
Display
Location of Malfunction
Contents of Malfunction
Details of
Malfunction
(Reference
Page)
Other
than PC
Board
PC Board
Outdoor
Unit
Indoor
Unit
Remote
Controller
U4
—
Transmission error
(between indoor and
outdoor unit)
156
U5
—
Transmission error
(between indoor and
remote controller)
157
U8
—
Transmission error
between “main” remote
controller and “sub” remote
controller
158
UA
—
—
Excessive indoor units
connected to this system.
159
UC
—
—
Centralized address setting
error
161