Troubleshooting for Indoor Unit
Si21-205
144
Troubleshooting
Troubleshooting
Remove the float switch from
X15A, short-circuit X15A, and
restart operation.
Is the
drainwater level
abnormally
high?
Does the drain
pump turn after restarting
operation?
Is a drain
pump connected to the
indoor unit PC
board?
Is there continuity?
YES
YES
YES
Is the
short-circuit
connector connected to
X15A on the indoor unit
PC board?
NO
NO
NO
Is the float
switch connected to
X15A?
NO
NO
NO
NO
NO
Is drain
raising mechanism
connected?
YES
YES
YES
Does
display of malfunction
“A3”appear?
YES
YES
220-240 VAC?
YES
NO
Continuity check of short-circuit
connector
Set to“emergency” and check
the voltage of X25A.
If “A3” is detected by a PC board
which is not mounted with X15A,
the PC board is defective.
Short-circuit connector
connection
Short-circuit connector
replacement
Indoor unit PC board
replacement
Connect drain pump
Malfuncton of drain system
Froat switch connection
Float switch replacement
Indoor unit PC board
replacement
Drain pump replacement
Indoor unit PC board
replacement
(S2732)
Caution
Be sure to turn off power switch before connect or disconnect connector,
or parts damage may be occurred.
Summary of Contents for Sky Air B-Series R-410A
Page 7: ...Si21 205 vi Table of Contents ...
Page 15: ...Models Si21 205 4 Model Name and Power Supply ...
Page 16: ...Si21 205 Functions 5 Part 2 Functions 1 List of Functions 6 ...
Page 35: ...Wireless Remote Controller Si21 205 24 Remote Controller ...
Page 79: ...Settings Concerning Maintenance Si21 205 68 Field Setting Detail of PCB 2 ...
Page 83: ...Maintenance Mode Setting Si21 205 72 Field Setting ...
Page 239: ...Troubleshooting for Outdoor Unit 50 60 class Si21 205 228 Troubleshooting ...
Page 321: ...Outdoor Unit 50 60 class Si21 205 310 Removal Procedure ...