Si21-205
Outdoor Unit (25/35 class)
Removal Procedure
283
3.8
Removal of Compressor
Procedure
Warning
Be sure to wait 10 minutes or more after turning off all power supplies
before disassembling work
.
Step
Procedure
Points
1. Remove the parts around
the compressor.
Be careful so as not to burn
the compressor terminals or
the name plate.
1
Remove the
terminal
cover
and the lead
wires of the
compressor so as not
to be burnt out by a gas
brazing machine.