FFQ25/35/50/60BV1B
Si21-205
248
Removal Procedure
5
Reinstall the lead wire
of thermistor and anti
sweat tube on the
original position by
using two pieces of
heat resistance tie
wrap.
∗
Heat resistance tie wrap
Parts No.:1278921
(Drg No.:4SA90202-1)
6
Put the heat exchanger
partition plate inside
and fix them with two
screws.
7
Pass the thermistor
ass'y through the
clamps and the slit of
partition plate securely
as the original state.
Pass the lead wire of
motor also through the
clamp securely.
8
Insert the grounding
terminal to the header.
Step
Procedure
Points
(S2673)
Anti sweat tube
(S2672)
Heat exchanger
partition plate
Fan motor lead wire
Clamp
Clamps
Slit of partition plate
Fan motor lead wire
Thermistor ass'y
(S2683)
(S2684)