![background image](http://html1.mh-extra.com/html/daikin/sky-air-b-series-r-410a/sky-air-b-series-r-410a_service-manual_2460071063.webp)
Field Piping and Wiring
Si21-205
52
Field Piping and Wiring
Observe the notes mentioned below when wiring to the terminals.
Tightening torque for the terminal screws.
•
Use the correct screwdriver for tightening the terminal screws. If the blade of screwdriver is
too small, the head of the screw might be damaged, and the screw will not be properly
tightened.
•
If the terminal screws are tightened too hard, screws might be damaged.
•
Refer to the table below for the tightening torque of the terminal screws.
Precautions to be taken for power supply wiring
Use a round crimp-style terminal for connection to the power supply terminal block.
In case it cannot be used due to unavoidable reasons, be sure to observe the following
instructions. (Refer to Fig. 30)
•
Do not connect wires of different gauge to the same power supply terminal. (Looseness in
the connection may cause overheating.) (Refer to Fig. 31)
•
When connecting wires of the same gauge, connect them according to. (Refer to Fig. 31)
•
In wiring, make certain that prescribed wires are used, carry out complete connections, and
fix the wires so that external forces are not applied to the terminals.
Terminal
Size
Tightening torque
Remote controller terminal block (2P)
M3.5
0.79 - 0.97 N•m
Power supply terminal block (3P)
M4
1.18 - 1.44 N•m
Ground terminal
M4
1.18 - 1.44 N•m
Electric wire
Round crimp-style terminal
Attach insulation sleeve
Fig. 30
Good
Wrong
Wrong
Connect wires of the
same gauge to both
side. (GOOD)
Do not connect wires
of the same gauge to
one side. (WRONG)
Do not connect wires
of different gauges.
(WRONG)
Fig. 31
Summary of Contents for Sky Air B-Series R-410A
Page 7: ...Si21 205 vi Table of Contents ...
Page 15: ...Models Si21 205 4 Model Name and Power Supply ...
Page 16: ...Si21 205 Functions 5 Part 2 Functions 1 List of Functions 6 ...
Page 35: ...Wireless Remote Controller Si21 205 24 Remote Controller ...
Page 79: ...Settings Concerning Maintenance Si21 205 68 Field Setting Detail of PCB 2 ...
Page 83: ...Maintenance Mode Setting Si21 205 72 Field Setting ...
Page 239: ...Troubleshooting for Outdoor Unit 50 60 class Si21 205 228 Troubleshooting ...
Page 321: ...Outdoor Unit 50 60 class Si21 205 310 Removal Procedure ...