Si21-205
Method of Field Set (Reset after Maintenance Inspection/Repair)
Field Setting
55
1.2
Field Setting
1.2.1 Wired Remote Controller
Notes:
(Field setting must be made from the remote controller in accordance with the installation
conditions.)
Setting can be made by changing the “Mode number”, “FIRST CODE NO.”, and “SECOND
CODE NO.”.
Refer to the following procedures for Field setting.
Procedure
When in the normal mode, press the
button for a minimum of four seconds, and the FIELD
SET MODE is entered.
Select the desired MODE NO. with the
button.
During group control, when setting by each indoor unit (mode No. 20, 21 and 23 have been
selected), push the
button and select the INDOOR UNIT NO to be set. (This operation is
unnecessary when setting by group.)
Push the
upper button and select FIRST CODE NO.
Push the
lower button and select the SECOND CODE NO.
Push the
button once and the present settings are SET.
Push the
button for about one second to return to the NORMAL MODE.
(Example) If during group setting and the time to clean air filter is set to FILTER CONTAMINATION -
HEAVY, SET MODE NO. to “10,” FIRST CODE NO. to “0,” and SECOND CODE NO. to “02.”
UNIT NO.
SECOND
CODE NO.
FIRST
CODE NO.
MODE NO.
FIELD
SET
MODE
Summary of Contents for Sky Air B-Series R-410A
Page 7: ...Si21 205 vi Table of Contents ...
Page 15: ...Models Si21 205 4 Model Name and Power Supply ...
Page 16: ...Si21 205 Functions 5 Part 2 Functions 1 List of Functions 6 ...
Page 35: ...Wireless Remote Controller Si21 205 24 Remote Controller ...
Page 79: ...Settings Concerning Maintenance Si21 205 68 Field Setting Detail of PCB 2 ...
Page 83: ...Maintenance Mode Setting Si21 205 72 Field Setting ...
Page 239: ...Troubleshooting for Outdoor Unit 50 60 class Si21 205 228 Troubleshooting ...
Page 321: ...Outdoor Unit 50 60 class Si21 205 310 Removal Procedure ...