![background image](http://html1.mh-extra.com/html/daikin/sky-air-b-series-r-410a/sky-air-b-series-r-410a_service-manual_2460071284.webp)
Si21-205
Outdoor Unit (25/35 class)
Removal Procedure
273
3.4
Removal of Propeller Fan and Fan Motor
Procedure
Warning
Be sure to wait 10 minutes or more after turning off all power supplies
before disassembling work
.
Step
Procedure
Points
1. Disconnect the fan motor
connector S70.
Remove the external plates
and the drip proof cover
protecting the electric parts.
Be sure to avoid forgetting to
restore the shelter and to
avoid losing or damaging it.
When restoring, match the
mark of the propeller fan with
the D-cut of the motor shaft.
The fan should be restored
so that the mark
will be at
upper part of the fan motor.
1
Release the lead-wires
of the fan motor from
the groove of the
switch box.
2
The propeller fan can
be removed when the
washer faced nut (M8)
is removed.
3
Remove two screws for
removing the fan
motor. The lead wires
are disengaged by
raising the hooks which
fix the lead wires.
Summary of Contents for Sky Air B-Series R-410A
Page 7: ...Si21 205 vi Table of Contents ...
Page 15: ...Models Si21 205 4 Model Name and Power Supply ...
Page 16: ...Si21 205 Functions 5 Part 2 Functions 1 List of Functions 6 ...
Page 35: ...Wireless Remote Controller Si21 205 24 Remote Controller ...
Page 79: ...Settings Concerning Maintenance Si21 205 68 Field Setting Detail of PCB 2 ...
Page 83: ...Maintenance Mode Setting Si21 205 72 Field Setting ...
Page 239: ...Troubleshooting for Outdoor Unit 50 60 class Si21 205 228 Troubleshooting ...
Page 321: ...Outdoor Unit 50 60 class Si21 205 310 Removal Procedure ...