Troubleshooting for Outdoor Unit (25/35 class)
Si21-205
172
Troubleshooting
Troubleshooting
Check No.12
Refer to P.193
Turn off the power and turn it on
again.
C
heck No.
12
Check the capacitor voltage.
Replace the outdoor unit
PCB.
* Inverter checker
Part No.: 1225477
Correct the power supply or
replace the SPM.
(Replace the outdoor unit
PCB.)
Replace the outdoor unit
PCB.
Replace the compressor.
Replace the outdoor unit
PCB.
Check the supply voltage.
(R3042)
Caution
Be sure to turn off power switch before connect or disconnect connector,
or parts damage may be occurred.
∗
Running current
as shown at right with relay
cable 1 or 2?
YES
Current
(guideline)
2 sec
Time
Rising with increasing
frequency
Capacitor charged when
the indoor unit or outdoor
unit main relay turns on
NO
NO
DC290~380V?
YES
Voltage within
the allowable range (Supply
voltage±15%)?
YES
NO
Any LED off?
Compressor running?
YES
NO
YES
NO
Get the system started.
Measure the rectifier input voltage.
Turn off the power. Disconnect the
harnesses U, V and W.
Check with the inverter checker (
∗
).
Turn off the power and reconnect
the above harnesses. Then turn on
the power again and get the
system restarted.
Summary of Contents for Sky Air B-Series R-410A
Page 7: ...Si21 205 vi Table of Contents ...
Page 15: ...Models Si21 205 4 Model Name and Power Supply ...
Page 16: ...Si21 205 Functions 5 Part 2 Functions 1 List of Functions 6 ...
Page 35: ...Wireless Remote Controller Si21 205 24 Remote Controller ...
Page 79: ...Settings Concerning Maintenance Si21 205 68 Field Setting Detail of PCB 2 ...
Page 83: ...Maintenance Mode Setting Si21 205 72 Field Setting ...
Page 239: ...Troubleshooting for Outdoor Unit 50 60 class Si21 205 228 Troubleshooting ...
Page 321: ...Outdoor Unit 50 60 class Si21 205 310 Removal Procedure ...