Troubleshooting for Outdoor Unit (25/35 class)
Troubleshooting
191
6.15.7 Outdoor Unit Fan System Check (With AC Motor)
Check No.9
Check the
fan motor lead wire
connector for secure
connection.
Abnormal
YES
NO
NO
Continuity
Are the
resistance at connector
leads
∞
? 1. red - black,
2. white - black
Check the fan
capacitor for continuity.
Does the outdoor
fan rotate?
Does
the outdoor unit fan
start just after the power
is turned on?
Check the outdoor fan system.
YES
YES
NO
Normal
No continuity
Repair.
Replace the fan motor.
Replace the fan motor.
Replace the outdoor unit PCB.
The outdoor fan system is
normal.
(R2670)