Si21-205
Troubleshooting for Indoor Unit
Troubleshooting
157
5.13 Transmission Error (Between Indoor Unit and Remote
Controller)
Remote
Controller
Display
U5
Applicable
Models
FFQ-B, FHQ-BU
Method of
Malfunction
Detection
Microcomputer checks if transmission between indoor unit and remote controller is normal.
Malfunction
Decision
Conditions
When transmission is not carried out normally for a certain amount of time
Supposed
Causes
Failure of remote controller
Failure of indoor PC board
Outside cause (noise, etc.)
Connection of 2 master remote controllers (When using 2 remote controllers)
Troubleshooting
Set one of the remote
controllers to"sub,"turn
off the power supply
temporarily, then restart
operation.
Indoor unit PC board
replacement
Malfunction could be
produced by noise.
Check the surrounding
area and restart
operation.
Change to double-core
independent cable.
Failure of remote
controller PC board or
replacement of
defective indoor unit PC
board
Malfunction could be
produced by noise.
Check the surrounding
area and restart
operation.
All indoor unit
PC board microcomputer
normal monitors
blinking
Control by 2
remote controllers
NO
YES
YES
YES
YES
YES
Resets
normally when power
supply is turned off
temporarily.
NO
(S2041)
SS1 of both
remote controllers is
set to "main."
YES
NO
NO
NO
Is it good
condition from noise
interference?
Using multicore
transmission wiring
between indoor unit and
remote controller
Caution
Be sure to turn off power switch before connect or disconnect connector,
or parts damage may be occurred.
Summary of Contents for Sky Air B-Series R-410A
Page 7: ...Si21 205 vi Table of Contents ...
Page 15: ...Models Si21 205 4 Model Name and Power Supply ...
Page 16: ...Si21 205 Functions 5 Part 2 Functions 1 List of Functions 6 ...
Page 35: ...Wireless Remote Controller Si21 205 24 Remote Controller ...
Page 79: ...Settings Concerning Maintenance Si21 205 68 Field Setting Detail of PCB 2 ...
Page 83: ...Maintenance Mode Setting Si21 205 72 Field Setting ...
Page 239: ...Troubleshooting for Outdoor Unit 50 60 class Si21 205 228 Troubleshooting ...
Page 321: ...Outdoor Unit 50 60 class Si21 205 310 Removal Procedure ...